Spectrum Controls 1756sc-IF8u User Manual
Page 55
Chapter 5:
Channel Configuration, Data, and Status
43
Channel Specific
Settings
The following settings allow you to configure individual channel
parameters. Each channel, 0 through 7, has these tags.
Channel On/Off:
.DisableChannel
0, 1
BOOL
0: Channel is enabled.
1: Channel is disabled.
You may decrease the module sampling time by disabling unused channels.
Input Range/Type
.RangeType
0-37
INT
You can select from a series of operational ranges for each channel on
your module. The range designates the minimum and maximum signals
that are detectable by the module. In the case of thermocouple or RTD
sensors the selected type dictates the linearization curve of the particular
sensor.
0 = -0.05 to 0.05V (-0.075 to 0.075V)
19 = RTD 1000Ω Ni 618
1 = -0.15 to 0.15V (-0.175 to 0.175V)
20 = RTD 120Ω Ni 672
2 = 0 to 5V (-0.5 to 5.5V)
21 = RTD 10Ω Cu 426
3 = 1 to 5V (0.5 to 5.5V)
22 = RTD 604Ω Ni-Fe 518
4 = 0 to 10V (-0.5 to 10.0V)
23 = Resistance 0 to 250Ω
5 = -10.0 to 10.0V
24 = Resistance 0 to 500Ω
6 = 0 to 20mA (0 to 21.5mA)
25 = Resistance 0 to 1000Ω
7 = 4 to 20mA (3.5 to 21.5mA)
26 = Resistance 0 to 2000Ω
8 = RTD 100Ω Pt 385
27 = Resistance 0 to 3000Ω
9 = RTD 200Ω Pt 385
28 = Resistance 0 to 4000Ω
10 = RTD 500Ω Pt 385
29 = TC Type J
11 = RTD 1000Ω Pt 385
30 = TC Type K
12 = RTD 100Ω Pt 3916
31 = TC Type T
13 = RTD 200Ω Pt 3916
32 = TC Type E
14 = RTD 500Ω Pt 3916
33 = TC Type R
15 = RTD 1000Ω Pt 3916
34 = TC Type S
16 = RTD 120Ω Ni 618
35 = TC Type B
17 = RTD 200Ω Ni 618
36 = TC Type N
18 = RTD 500Ω Ni 618
37 = TC Type C