Channel Configuration, Data, and Status

43

Channel Specific

Settings

The following settings allow you to configure individual channel

parameters. Each channel, 0 through 7, has these tags.
Channel On/Off:
.DisableChannel

0, 1

BOOL

0: Channel is enabled.

1: Channel is disabled.

You may decrease the module sampling time by disabling unused channels.

Input Range/Type
.RangeType

0-37

INT

You can select from a series of operational ranges for each channel on

your module. The range designates the minimum and maximum signals

that are detectable by the module. In the case of thermocouple or RTD

sensors the selected type dictates the linearization curve of the particular

sensor.

0 = -0.05 to 0.05V (-0.075 to 0.075V)

19 = RTD 1000Ω Ni 618

1 = -0.15 to 0.15V (-0.175 to 0.175V)

20 = RTD 120Ω Ni 672

2 = 0 to 5V (-0.5 to 5.5V)

21 = RTD 10Ω Cu 426

3 = 1 to 5V (0.5 to 5.5V)

22 = RTD 604Ω Ni-Fe 518

4 = 0 to 10V (-0.5 to 10.0V)

23 = Resistance 0 to 250Ω

5 = -10.0 to 10.0V

24 = Resistance 0 to 500Ω

6 = 0 to 20mA (0 to 21.5mA)

25 = Resistance 0 to 1000Ω

7 = 4 to 20mA (3.5 to 21.5mA)

26 = Resistance 0 to 2000Ω

8 = RTD 100Ω Pt 385

27 = Resistance 0 to 3000Ω

9 = RTD 200Ω Pt 385

28 = Resistance 0 to 4000Ω

10 = RTD 500Ω Pt 385

29 = TC Type J

11 = RTD 1000Ω Pt 385

30 = TC Type K

12 = RTD 100Ω Pt 3916

31 = TC Type T

13 = RTD 200Ω Pt 3916

32 = TC Type E

14 = RTD 500Ω Pt 3916

33 = TC Type R

15 = RTD 1000Ω Pt 3916

34 = TC Type S

16 = RTD 120Ω Ni 618

35 = TC Type B

17 = RTD 200Ω Ni 618

36 = TC Type N

18 = RTD 500Ω Ni 618

37 = TC Type C