Spectrum Controls 1756sc-IF8u User Manual
Page 50
![background image](/manuals/742124/50/background.png)
38
ControlLogix
™
Universal Analog Input Module
Note: If an invalid configuration is sent to the module a connection error
will occur. See chapter 7 for a list of error codes.
Configuration Tags
The following Global Module Settings and Channel Specific Settings
sections allow custom configuration of the module. These tags can be
found within the IF8u_config controller tag.
Global Module
Settings
The following tag settings are module related:
Configuration Management
Configuration Management
Configuration Management
Configuration Management
Configuration Management
.ConfigRevNumber
0, 1
BOOL
0: The module will always accept this configuration if valid. This value
must be used for on-the-fly configuration changes.
1: In multiple owner systems if there is already a connection to the module
then this configuration must match the one of the current connection in
order for this controller to connect to the module.Channel On/Off
Note: The Module Reconfigure message instruction sets this parameter to
zero.
Temperature Measurement:
.RemoteTermination
0, 1
BOOL
Not Used.
.CJDisable
0, 1
BOOL
0: The cold junction compensation terminal block thermistors will be read.
Thermocouple input values will be compensated based on the thermistor
readings.
1: The cold junction compensation thermal block thermistors will not be
read. Thermocouple input values will be compensated with the default 25
degC value plus CJCOffset.
Note: 2 thermistors have been provided with the module to be installed on
your terminal block if cold junction compensation is to be used.
.TempMode
0, 1
BOOL
0: Temperatures for thermocouples, RTDs and the cold junction
thermistors will be displayed in degrees Celsius.