Exposed Junction Thermocouples

As shown in the illustration that follows, using exposed junction
thermocouples may result in removal of channel to channel isolation. This
may occur if multiple exposed thermocouples are in direct contact with
electrically conductive process material. To prevent violation of channel to
channel isolation:

• For multiple exposed thermocouples, do not allow the measuring

junction of the thermocouple to make direct contact with electrically
conductive process material.

• Use a single exposed junction thermocouple with multiple ungrounded

junction thermocouples.

• Use all ungrounded junction thermocouple instead of the exposed

junction type.

+
-

CH3

+
-

CH0

MUXES

1756sc-IF8u

Exposed junction with shielded cable