The “Additional Fault Code” value details the configuration error if the
“(16#0009) module configuration rejected: Parameter Error” was
received.
Global Errors
16#0F04 - .ConfigurationRevError
If the .ConfigurationRevNumber tag is 1 and a second owner
attempts to connect with a different configuration, this error
will occur. You must adjust the second owners configuration
to match the first.
16#0F05 - .ConfiguratinRevNumber Error
An invalid value has been entered into this tag.
16#0F06 - .CyclicalAutocalPeriod Error
An invalid value has been entered into this tag.
16#0F07 - .RealTimeSample Error
An invalid value has been entered into this tag.
16#0F08 - .CJOffset
An invalid value has been entered into this tag.
Channel Specific Errors
Note: n = channel number (0-7)
16#0n01 - .RangeType Error
An invalid value has been entered into this tag.
16#0n02 - .ADCFilter Error
An invalid value has been entered into this tag.
16#0n03 - .TenOhmOffset Error
An invalid value has been entered into this tag.
16#0n04 - .DigitalFilter Error
An invalid value has been entered into this tag.
16#0n05 - .RateAlarmLimit Error
An invalid value has been entered into this tag.
16#0n06 - .AlarmDeadband Error
An invalid value has been entered into this tag.
Note: If there are multiple errors in the configuration tags only one will be
displayed at a time. Once the displayed error has been corrected, the
additional errors will be displayed upon reconnection to the module. Each
error must be resolved before a running connection will be allowed.