beautypg.com

Delta Electronics AC Motor Drives VFD-XXXE User Manual

Page 17

background image

English- 17

Pr.

Explanation

Settings

Factory

Setting

NOTE

03.05 Terminal

Count

Value

0 to 9999

0

03.06

Preliminary Count
Value

0 to 9999

0

03.07

EF Active When
Terminal Count
Value Attained

0: Terminal count value attained, no EF
display
1: Terminal count value attained, EF active

0

03.08 Fan

Control

0: Fan always ON
1: 1 minute after AC motor drive stops, fan
will be OFF
2: Fan ON when AC motor drive runs, fan
OFF when AC motor drive stops
3: Fan ON when preliminary heatsink
temperature attained

0

03.09

The Digital Output
Used by PLC
(NOT for VFD*E*C
models)

Read only
Bit0=1:RLY used by PLC
Bit1=1:MO1 used by PLC
Bit2=1:MO2/RA2 used by PLC
Bit3=1:MO3/RA3 used by PLC
Bit4=1:MO4/RA4 used by PLC
Bit5=1:MO5/RA5 used by PLC
Bit6=1:MO6/RA6 used by PLC
Bit7=1:MO7/RA7 used by PLC

##

03.10

The Analog Output
Used by PLC
(NOT for VFD*E*C
models)

Read only
Bit0=1:AFM used by PLC
Bit1=1: AO1 used by PLC
Bit2=1: AO2 used by PLC

##

03.11

Brake Release
Frequency

0.00 to 20.00Hz

0.00

03.12

Brake Engage
Frequency

0.00 to 20.00Hz

0.00

03.13

Display the Status of
Multi-function
Output Terminals

Read only
Bit0: RLY Status
Bit1: MO1 Status
Bit2: MO2/RA2 Status
Bit3: MO3/RA3 Status
Bit4: MO4/RA4 Status
Bit5: MO5/RA5 Status
Bit6: MO6/RA6 Status
Bit7: MO7/RA7 Status

##

03.14 Desired

Frequency

2 Attained

0.00 to 600.0Hz

0.00

Group 4 Input Function Parameters

a

04.00

Keypad
Potentiometer Bias

0.0 to 100.0 %

0.0

a

04.01

Keypad
Potentiometer Bias
Polarity

0: Positive bias
1: Negative bias

00

a

04.02

Keypad
Potentiometer Gain

0.1 to 200.0 %

100.0