HORIZONTAL INSTALLATION

EXHAUST VENT TERMINATION SHALL BE AS FOLLOWS:

A MINIMUM OF 4 FEET/1220 mm BELOW, BESIDE, AND 1 FOOT ABOVE ANY DOOR OR
WINDOW THAT OPENS, OR ANY OPENING INTO A BUILDING.

A MINIMUM OF 2 FEET/610 mm FROM ANY ADJACENT BUILDING OR OVERHANG.

A MINIMUM OF 7 FEET/2130 mm ABOVE GRADE, WHEN LOCATED ADJACENT TO
PUBLIC WALKWAYS.

A MINIMUM OF 2 FEET/610 mm ABOVE GRASS, PLANTS OR OTHER COMBUSTIBLES.





Note: The pipe lengths shown are for reference only.
Your actual pipe length requirements may differ.


SINGLE WALL PIPE SHALL NOT BE
USED FOR ANY INSTALLATION.

HORIZONTAL INSTALLATION SHALL
BE A MAXIMUM OF 5’ FEET.


















WARNING:
Vent surfaces can become hot enough to cause burns
if touched. Non-combustible shielding may be required.

PLEASE FOLLOW THE PIPE MANUFACTURER’S INSTRUCTIONS AND LOCAL BUILDING CODES FOR

THE CLEARANCE TO COMBUSTIBLES REQUIRED FOR INSTALLATION OF THE VENT PIPE BEING USED.