beautypg.com

Care and maintenance, I. filter assembly, Ii. cooling coil, drain ran, and condensate drain – Bryant FA4A User Manual

Page 17: Iii. blower motor and wheel, Care and maintenance -ls, Blower motor and wheel

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

AÏÏG/14/2008/THÏÏ 03:49 PM UTC TECH PUB

FAX No. 317 240 5662

P. 017

a. Attach manifold/gage set to service valves,

b. Front scat (close) liquid tube service valve,

c. Start yirit in cooling mode.

d. Run unit until vapor pressure reaches 5 pSig (35kPa).

c. Turn off electrical supply to outdoor unit.

f. Front seat vapor

Service

valve.

g. Recover any remaining refrigerant.

NOTE: All outdoor unit coils will hold only factory-supplied
amount of

refrigerant.

E?tcess refrigerant, such as in long-tube

applications, may cause compressor internal pressure relief valve

to open (indicated by sudden rise in vapor pressure) before vapor
pressure reaches 5 psig (35Ji:Pa). If this occurs, turn off electrical
supply to outdoor unit immediately, front seat vapor service valve,
and recover any remaining refrigerant.

2. Turn off electrical supply to indpor unit.

3. Disconnect condensate drain tube,

4. Disconnect liquid and vapor tubes from indoor coil. Use

either a tubing cutter to cut tubes or a torch to unbrace tubes
as required.

NOTE: If a torch Is used to unbraze line set, protect fitting panel

with a wet doth or br^e shield, as necessary. System contains oil

vapors which may ignite when ejeposed to a flame.

5. Remove coil access and fitting panels.

6. Remove 1 screw securing coil to unit casing.

7. Remove coil/pan assembly from unit.

8. Place assembly oti; a flat surface. Removc=2 screws securing

coil support columns to pan. (See Fig. 15.)

9. Rotate columns 90“, pull away from coil, and remove

columns from assembly.

10. Remove remaining 2 screws securing coil to condensate

pan,

11. Remove coil from condensate pan.

12. Remove coil top seal, (See Fig. 15.)

.13. Install new coil into condensate pan using 2 original screws

and 2 support columns.

NOTE: Correct coil position in condensate pan is essential to

reliable operation.

14. Install new coil/pan assembly into unit. Secure with 2

Sci:c'vv5 previously removed from unit casing,

15. Reinstall coil access and fitting panels.

16. Reconnect liquid and vapor refrigerant tubes, and conden­

sate drain tiibe. Install fr]t6r-drier(s), if necessary.

17. Evacuate tube set and indoor coil, back scat (open) liquid

and vapor service valves.

18. Turn on electrical supplies to indoor and outdoor units.

19- Check system refrigerant charge and operation. See ''Split-

System Residential Air^Gonditioners and Heat-Tumps
Service Manual" for further information.

CARE AND MAINTENANCE

To continue high performance, and minimize possible equipment
failure, it is essential periodic maintenance be performed on this
equipment,

11)6 ability to properly perform maiuteuauce on this equipment
requires certain mechanical skills and tools- The only consumer
service recommended or required is filter maintenance. (See Filter
Assembly.)

A

WARNING;

Disconnect all power to the unit before

servicing the field wires

Or

removing the control package.

The disconnect (when used) on the access panel does not
disconnect power to the line side of the disconnect, but
does allow safe

service

to all other parts of the unit.

Electrical shock can cause personal injury or death.

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect and clean or replace air filter each month or as

required.

2. Inspect cooling coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean as necessary. An

inspection port is provided on all A-coil delta plates.
Remove plastic plug to inspect. Replace plug after inspec­
tion.

3.

Inspect blower motor and wheel for cleanliness each

heating and cooling season. Clean as necessary.

4. Inspect electrical connections for tightness and controls for

proper operation each heating and cooling season. Service
as necessary.

A

WARNING:

As witja^any mechanical equipment, per­

sonal injury can .result frpm sharp metal edges. Be careful

^vyhen, removing,parts.

I. FILTER ASSEMBLY

To clean

Or

replace air filter, push plastic connectors toward center

of unit and remove filter access panel outward. -Push filter up and

back into unit. Then slide filter out. Clean filter by tising cold
water and mild detergent. Rinse and allow filter to dry. No oiling
or coating of filter is required. New filters are available from your
local distributor. Place filter in slot with cross-mesh binding up or

facing cooling coil and replace filter access panel,

II.

COOLING COIL, DRAIN RAN, AND CONDENSATE

DRAIN

The cooling coil is easily cleaned when it is dry. Inspect the coil
and clean (if necessary) before each cooling season. To check or
clean cooling coil, rethov^ coil access paiidl. If coil is coated with
dirt or lint, vacuurn it' with a soft brush attachment.

Be careful not to bend coil fins. If coil is coated with oil or grease,

clean it with a mild detergent and water solution. Rinse coil

thoroughly with olpar water;^Be careful not,to splash water on

insulation,

Inspect drain pan and condensate drain at the same time cooling
coil is checked. Clean drain pan and condensate drain by removing

any foreign matter fitom pan. Flush pan and drain tube with clear

water.

If

drain

tube is restricted, it can generally be

cleared

by high-

pr'essure water. Cut plastic line and, work outside condensate pan

and away from coil to clpan drain tube, ,,

A

CAUTION:

Dp not use caustic household drain cleaners

in the condensate pan or near the coil. Drain cleaners can
quickly destroy a coil,'

III. BLOWER MOTOR AND WHEEL

Clean blower motor and wheel when cooling coil is cleaned.

-

17

-

This manual is related to the following products: