Bryant 551C User Manual
Installation instructions, Warning, Safety considerations
1
Installation Instructions
551B 036--072
551C 024--060
SINGLE--PACKAGE ROOFTOP ELECTRIC COOLING
UNITS WITH OPTIONAL ELECTRIC HEAT
TABLE OF CONTENTS
Page
SAFETY CONSIDERATIONS
1
. . . . . . . . . . . . . . . . . . . . . . . .
INSTALLATION
1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 1--Provide Unit Support
2
. . . . . . . . . . . . . . . . . . . . . .
ROOF CURB
2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLAB MOUNT (Horizontal Units Only)
2
. . . . . . . . . . .
ALTERNATE UNIT SUPPORT
2
. . . . . . . . . . . . . . . . .
Step 2--Field Fabricate Ductwork
2
. . . . . . . . . . . . . . . . . . .
Step 3--Install External Trap for Condensate Drain
2
. . . . . . .
Step 4--Rig and Place Unit
2
. . . . . . . . . . . . . . . . . . . . . . . . .
POSITIONING
4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Step 5 — Make Electrical Connections
8
. . . . . . . . . . . . . . . .
FIELD POWER SUPPLY
8
. . . . . . . . . . . . . . . . . . . . . .
FIELD CONTROL WIRING
8
. . . . . . . . . . . . . . . . . . . .
HEAT ANTICIPATOR SETTINGS
8
. . . . . . . . . . . . . . .
Step 6 — Adjust Factory-Installed Options
22
. . . . . . . . . . .
PERFECT HUMIDITY™ ADAPTIVE
DEHUMIDIFICATION SYSTEM
22
. . . . . . . . . . . . . .
DISCONNECT SWITCH
22
. . . . . . . . . . . . . . . . . . . . .
MANUAL OUTDOOR-AIR DAMPER
22
. . . . . . . . . .
CONVENIENCE OUTLET
22
. . . . . . . . . . . . . . . . . . .
OPTIONAL ECONOMI$ER IV
24
. . . . . . . . . . . . . . . .
ECONOMI$ER IV STANDARD SENSORS
25
. . . . . .
ECONOMI$ER IV CONTROL MODES
26
. . . . . . . . .
Step 7 — Adjust Evaporator-Fan Speed
31
. . . . . . . . . . . . . .
PRE--START--UP
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP
48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SERVICE
50
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TROUBLESHOOTING
57
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP CHECKLIST
61
. . . . . . . . . . . . . . . . . . . . . . . . . . .
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability,or operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
!
WARNING
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert
to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in
basepan of unit with insulation-side down. Seals around
openings must be tight. (See Fig. 1.)