DPG-21XX-00X Digital Controllers
Woodward
32
Wiring Diagrams
Cabling for DPG 21XX-00X controllers is limited to less than
30m (98.4’). Power cabling is limited to less than 10m (32.8’)
in total length. The wiring diagrams below show specific
cable types required.
DPG-2101-00X
Dimensions are in inches. [Dimensions in brackets are millimeters.]
Figure 1. Wiring Diagram for DPG-2101-001 and DPG-2101-002 Controllers
1
Connect the MPU shield at the controller end only. Connecting the shield at the MPU source end could
introduce noise due to ground loops and also disable the reverse battery protection feature.