beautypg.com

Chapter 6. installation instructions, Recommended mounting – Winco DPG-2145-001 User Manual

Page 38

background image

Manual 36526F

DPG-21XX-00X Digital Controllers

Woodward

30

Chapter 6.

Installation Instructions


Recommended Mounting


The DPG-21XX-00X controller is designed to be panel mounted and its chassis
electrically bonded to the same protective reference as the engine structure. The
mounting location should protect the controller from exposure to rain, weather, and
direct sunlight. The controller should not be mounted on the engine or in an
environment that exceeds the mechanical specifications outlined in Chapter 2 of this
manual. The controller should be mounted in a position to allow access to the user
interface, the COMM port and the terminal strip.

Terminal Descriptions

DPG-2101-00X

NO.

NAME

FUNCTION

1

BAT+

Battery positive (9

–30 Vdc)

2

BAT-

Battery negative

3

ACT

Actuator drive output

4

ACT

Actuator drive return

5

MPU+

Magnetic pickup signal input

6

MPU-

Magnetic pickup ground

7

SHIELD

Ground connection for cable shielding


DPG-2145-00X

NO.

NAME

FUNCTION

1

BAT+

Battery positive (9

–30 Vdc)

2

ACT

Actuator drive output

3

Not Labeled

Digital input common

4

INC

Digital input to increase selected set speed
(Active when tied to Pin 3)

5

IGN TACH

Ignition tachometer signal input

6

SET SPD 2

Set Speed B selected when this pin tied to
Pin 12

7

BAT-

Battery negative

8

ACT

Actuator drive return

9

SHIELD

Ground connection for cable shielding

10

DEC

Digital input to decrease selected set speed
(Active when tied to Pin 3)

11

IGN GND

Ignition ground signal

12

SET SPD 1

Set Speed A selected when this pin is open

This manual is related to the following products: