Chapter 6. installation instructions, Recommended mounting – Winco DPG-2145-001 User Manual
Page 38
Manual 36526F
DPG-21XX-00X Digital Controllers
Woodward
30
Chapter 6.
Installation Instructions
Recommended Mounting
The DPG-21XX-00X controller is designed to be panel mounted and its chassis
electrically bonded to the same protective reference as the engine structure. The
mounting location should protect the controller from exposure to rain, weather, and
direct sunlight. The controller should not be mounted on the engine or in an
environment that exceeds the mechanical specifications outlined in Chapter 2 of this
manual. The controller should be mounted in a position to allow access to the user
interface, the COMM port and the terminal strip.
Terminal Descriptions
DPG-2101-00X
NO.
NAME
FUNCTION
1
BAT+
Battery positive (9
–30 Vdc)
2
BAT-
Battery negative
3
ACT
Actuator drive output
4
ACT
Actuator drive return
5
MPU+
Magnetic pickup signal input
6
MPU-
Magnetic pickup ground
7
SHIELD
Ground connection for cable shielding
DPG-2145-00X
NO.
NAME
FUNCTION
1
BAT+
Battery positive (9
–30 Vdc)
2
ACT
Actuator drive output
3
Not Labeled
Digital input common
4
INC
Digital input to increase selected set speed
(Active when tied to Pin 3)
5
IGN TACH
Ignition tachometer signal input
6
SET SPD 2
Set Speed B selected when this pin tied to
Pin 12
7
BAT-
Battery negative
8
ACT
Actuator drive return
9
SHIELD
Ground connection for cable shielding
10
DEC
Digital input to decrease selected set speed
(Active when tied to Pin 3)
11
IGN GND
Ignition ground signal
12
SET SPD 1
Set Speed A selected when this pin is open