DPG-2155-00X & DPG-2145-00X Parameter List

PARAMETER LIST FOR DPG-2155-00X (MPU) & DPG-2145-00X (IGNITION)

(These controllers use the 12-terminal quick connect.)

PARAMETER NAME

DEFAULT

MINIMUM

MAXIMUM

Opt.

1. No. of Flywheel
Teeth or Pulses per
Revolution

-001

0

0

0

-002

0

0

572

Req.

2. Set Speed A

1000 (25)

Set Speed A Min

Set Speed A Max

Opt.

3. Set Speed B

1000 (25)

Set Speed B Min

Set Speed B Max

Opt.

4. Idle Speed

50 (20)

Idle Speed Min

Idle Speed Max

Req.

5. Proportional

25

1

99

Req.

6. Integral

50

0

99

Req.

7. Derivative

25

0

99

Req.

8. OVG @ Set Speed A

Use the controller’s built-in GAIN potentiometer

Opt.

9. OVG @ Set Speed B

20

1

99

Opt.

10. OVG @ Idle Speed

20

1

99

Req.

11. Gain Factor

20 (40)

1

99

Req.

12. Speed Filter

16 (4)

1

24

Opt.

13. Idle Hold Time

0

0

9999

Opt.

14. Accel Rate

1000 (3000)

1

9999

Opt.

15. Decel Rate

1000 (3000)

1

9999

Opt.

16. Startup Rate

1000 (3000)

1

9999

Opt.

17. Integral Low Limit

0

0

Integral High Limit

Opt.

18. Integral High Limit

99

Integral Low Limit

99

Opt.

19. Password

0

0

99

Opt.

20. Over Speed Limit

-001

100

0

100

-002

15000 (450)

0

15000 (450)

Opt.

21. Set Speed A Min

10 (2)

10 (2)

Set Speed A

Opt.

22. Set Speed A Max

11000 (300)

Set Speed A

11000 (300)

Opt.

23. Set Speed B Min

10 (2)

10 (2)

Set Speed A

Opt.

24. Set Speed B Max

11000 (300)

Set Speed B

11000 (300)

Opt.

25. Idle Speed Min

10 (2)

10 (2)

Idle Speed

Opt.

26. Idle Speed Max

11000 (300)

Idle Speed

11000 (300)

Opt.

27. Duty Cycle Limit

95

10

95

Req.

28. Startup Speed

1000 (25)

10 (2)

11000 (300)

Opt.

29. Startup Duty Cycle

30

5

95

Req. = Parameter adjustment required to achieve Basic Governing

Opt. = Parameter use is optional

Default, Minimum and Maximum values in parenthesis apply when the controller uses ignition pulses to

sense engine speed, which would be the case for a DPG-2145-00X controller.


Note: All Speed and Rate values are shown as Hertz values (parameters 2-4, 14-16, 20-26).
Changing the value of parameter 1 will cause different default values to be displayed based on
the Hertz to RPM formula.

This manual is related to the following products: