DPG-21XX-00X Digital Controllers
Woodward
6
DPG-2101-00X & DPG-2146-00X Parameter List
PARAMETER LIST FOR DPG-2101-00X (MPU) & DPG-2146-00X (IGNITION
)
(These controllers use the 7-terminal Euro style screw terminal connector.)
PARAMETER NAME
DEFAULT
MINIMUM
MAXIMUM
Opt.
1. No. of Flywheel
Teeth or Pulses per
revolution
-001
0
0
0
-002
0
0
572
Req.
2. Set Speed A
1000 (25)
Set Speed A Min
Set Speed A Max
3. Not Available
Opt.
4. Idle Speed
50 (20)
Idle Speed Min
Idle Speed Max
Req.
5. Proportional
25
1
99
Req.
6. Integral
50
0
99
Req.
7. Derivative
25
0
99
Req.
8. OVG @ Set Speed A
Use the controller’s built-in GAIN potentiometer
9. Not Available
Opt.
10. OVG @ Idle Speed
20
1
99
Req.
11. Gain Factor
20 (40)
1
99
Req.
12. Speed Filter
16 (4)
1
24
Opt.
13. Idle Hold Time
0
0
9999
Opt.
14. Accel Rate
1000 (3000)
1
9999
Opt.
15. Decel Rate
1000 (3000)
1
9999
Opt.
16. Startup Rate
1000 (3000)
1
9999
Opt.
17. Integral Low Limit
0
0
Integral High Limit
Opt.
18. Integral High Limit
99
Integral Low Limit
99
Opt.
19. Password
0
0
99
Opt.
20. Over Speed Limit
-001
100
0
100
-002
15000 (450)
0
15000 (450)
Opt.
21. Set Speed A Min
10 (2)
10 (2)
Set Speed A
Opt.
22. Set Speed A Max
11000 (300)
Set Speed A
11000 (300)
23. Not Available
24. Not Available
Opt.
25. Idle Speed Min
10 (2)
10 (2)
Idle Speed
Opt.
26. Idle Speed Max
11000 (300)
Idle Speed
11000 (300)
Opt.
27. Duty Cycle Limit
95
10
95
Req.
28. Startup Speed
1000 (25)
10 (2)
11000 (300)
Opt.
29. Startup Duty Cycle
30
5
95
Req. = Parameter adjustment required to achieve Basic Governing
Opt. = Parameter use is optional
Default, Minimum and Maximum values in parenthesis apply when the controller uses ignition pulses to
sense engine speed, which would be the case for a DPG-2146-00X controller
Note: All Speed and Rate values are shown as Hertz values (parameters 2, 4, 14-16, 20-22, 25-
26). Changing the value of parameter 1 will cause different default values to be displayed based
on the Hertz to RPM formula.