beautypg.com

A.2 door holder device, A.3 two-wire smoke detectors – SilentKnight 5895XL 6A Intelligent Remote Power Supply User Manual

Page 46

background image

Model 5895XL Intelligent Power Module Installation and Operation Manual

A-12

151142

A.2

Door Holder Device

The following UL listed door holder can be used with the 5895XL: ESL DHS-1224

A.3

Two-Wire Smoke Detectors

Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is
organized by manufacturer. The columns show the number of detectors per loop that can be
used.

The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of
the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.

Do not mix different models of detectors on any zone; false alarms could occur.

Do not mix detectors of different models unless the system is specifically intended to be installed in that
configuration.

Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset
time of the smoke detector.

Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The
table is organized by manufacturer. The columns show the number of detectors per loop that
can be used.

5895XL

Identifier

24H

Operating Voltage Range

18.5–27.4 VDC

Table A-2: Compatible Two-Wire Smoke Detectors

Manufacturer

Model Name or Number

(Base model name or number in

parentheses.)

Compatibility ID

# per Loop

Head

Base

Apollo

55000-350 (45681-200)

55000-350

45681-200

24 / loop

55000-250 (45681-200)

55000-250

45681-200

24 / loop

Apollo

55000-225

55000-225

45681-255,
226, 256

45681-200,
220, 230,
232, 251,
252

15 / loop for

Ion Detectors

15 / loop for

Photo Electric

Detectors

55000-226

55000-226

55000-227

55000-227

55000-325

55000-325

55000-328

55000-328

55000-326

55000-326

55000-327

55000-327