Door Holder Device
The following UL listed door holder can be used with the 5895XL: ESL DHS-1224
A.3
Two-Wire Smoke Detectors
Table A-2 lists two-wire smoke detectors that are compatible with the panel. The table is
organized by manufacturer. The columns show the number of detectors per loop that can be
used.
The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of
the smoke detector. If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in that
configuration.
Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset
time of the smoke detector.
Table A-2 lists two-wire smoke detectors that are compatible with the 5895XL panel. The
table is organized by manufacturer. The columns show the number of detectors per loop that
can be used.
5895XL
Identifier
24H
Operating Voltage Range
18.5–27.4 VDC
Table A-2: Compatible Two-Wire Smoke Detectors
Manufacturer
Model Name or Number
(Base model name or number in
parentheses.)
Compatibility ID
# per Loop
Head
Base
Apollo
55000-350 (45681-200)
55000-350
45681-200
24 / loop
55000-250 (45681-200)
55000-250
45681-200
24 / loop
Apollo
55000-225
55000-225
45681-255,
226, 256
45681-200,
220, 230,
232, 251,
252
15 / loop for
Ion Detectors
15 / loop for
Photo Electric
Detectors
55000-226
55000-226
55000-227
55000-227
55000-325
55000-325
55000-328
55000-328
55000-326
55000-326
55000-327
55000-327