Model 5895XL Intelligent Power Module Installation and Operation Manual
3-12
151142
3.5.5
Installing 4-Wire Smoke Detectors
Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL panel (see
Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate
how to connect a UL listed four-wire detector to the control panel.
Installing a Class B 4-Wire Smoke Detector
Figure 3-14 illustrates how to install a 4-wire Class B smoke detector.
Conventions used for wiring 4-wire Class B loops:
1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at
once.
2. Each Class B loop input is paired with a unique power source as shown in Figure 3-14.
3. Each loop gets smoke power from the even numbered I/O circuit and the contact input is
connected to the odd numbered I/O circuit.
Figure 3-14 Class B 4-Wire Smoke Detector Connections
Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit
number used. For example, Figure 3-14 uses both I/O circuit 5 and 6, so in programming it would be
referred to as point 5.
Air Products
PAM-2
Model 160150
Supervision
Module
UL Listed
EOL Resistor
Model 7628
ESL 449CT
Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.