3.5.5

Installing 4-Wire Smoke Detectors

Any compatible U.L. listed four-wire smoke detector can be used with the 5895XL panel (see
Appendix A for list of compatible smoke detectors). Figure 3-12 and Figure 3-13 illustrate
how to connect a UL listed four-wire detector to the control panel.

Installing a Class B 4-Wire Smoke Detector

Figure 3-14 illustrates how to install a 4-wire Class B smoke detector.

Conventions used for wiring 4-wire Class B loops:

1. Up to three Class B 4-wire smoke detector loops can be connected to the control panel at

once.

2. Each Class B loop input is paired with a unique power source as shown in Figure 3-14.

3. Each loop gets smoke power from the even numbered I/O circuit and the contact input is

connected to the odd numbered I/O circuit.

Figure 3-14 Class B 4-Wire Smoke Detector Connections

Note: In programming any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit

number used. For example, Figure 3-14 uses both I/O circuit 5 and 6, so in programming it would be
referred to as point 5.

Air Products

PAM-2

Model 160150

Supervision

Module

UL Listed

EOL Resistor

Model 7628

ESL 449CT

Note:
I/O circuit 5 and 6
used as an example.
Any I/O point pairing
could be used.