2 current draw worksheet, 2 current draw worksheet -6, Eet, table 2-4 (section 2.6.2) – SilentKnight 5895XL 6A Intelligent Remote Power Supply User Manual
Page 16: Record this information in table 2-4 at line a, Rksheet (table 2-4) must be less than the

Model 5895XL Intelligent Power Module Installation and Operation Manual
2-6
151142
2.6.2
Current Draw Worksheet
For *each 5895XL in the installation, use this worksheet to determine current requirements
during alarm/battery standby operation. (Copy this page if additional space is required.)
*
Use a separate worksheet for each 5895XL.
**
If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because
power is removed during that time. However, during normal operation, door holders draw current and must be
included in the 6.0 A total current that can be drawn from the panel.
***
Use next size battery with capacity greater than required.
Table 2-4: Current Draw Calculations
Device
Number of
Devices
Current per Device
Standby
Current
Alarm Current
For each device use this formula:
This column
X This column
= Current per number of devices.
5895XL Intelligent Power Module
(Current draw from battery)
1*
Standby:
40 mA 40 mA
Alarm:
160 mA
160 mA
Additional 5895XL
(Daisy-chained to this module)
(7 max.)
Standby:
10 mA
Alarm:
10 mA
Addressable Devices
(381 max.)
Standby:
0.55 mA
Alarm:
0.55 mA
5815XL SLC Expander
(2 max.)
Standby:
55 mA
mA
Alarm:
55 mA
mA
5860 Remote Fire Alarm Annunciator
(8 max.)
Standby:
20 mA
mA
Alarm:
25 mA
mA
5824 Serial / Parallel Module
(2 max.)
Standby:
45 mA
mA
Alarm:
45 mA
mA
5865-4 LED Annunciator
(with reset and silence switches)
(8 max.)
Standby:
35 mA
mA
Alarm:
145 mA
mA
5865-3 LED Annunciator
Standby:
35 mA
mA
Alarm:
145 mA
mA
5880 Generic LED Driver Module
Standby:
35 mA
mA
Alarm:
200 mA
mA
A
Total System Current
**Auxiliary Devices
Refer to devices manual for current rating.
Alarm/Standby:
mA
mA
mA
Alarm/Standby:
mA
mA
mA
Alarm/Standby:
mA
mA
mA
Alarm/Standby:
mA
mA
mA
B
Auxiliary Devices Current
Alarm:
mA
mA
Alarm:
mA
mA
Alarm:
mA
mA
Alarm:
mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA
mA
E
Total current ratings converted to amperes (line D x .001):
A
A
F
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
H
G
Multiply lines E and F.
Total standby AH
AH
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
I
Multiply lines E and H.
Total alarm AH
AH
J
***Add lines G and I.
Total ampere hours required
AH