Model 5895XL Intelligent Power Module Installation and Operation Manual

2-6

151142

2.6.2

Current Draw Worksheet

For *each 5895XL in the installation, use this worksheet to determine current requirements
during alarm/battery standby operation. (Copy this page if additional space is required.)

*

Use a separate worksheet for each 5895XL.

**

If you are using door holders, you do not need to consider door holder current for alarm/battery standby, because
power is removed during that time. However, during normal operation, door holders draw current and must be
included in the 6.0 A total current that can be drawn from the panel.

***

Use next size battery with capacity greater than required.

Table 2-4: Current Draw Calculations

Device

Number of

Devices

Current per Device

Standby

Current

Alarm Current

For each device use this formula:

This column

X This column

= Current per number of devices.

5895XL Intelligent Power Module
(Current draw from battery)

1*

Standby:

40 mA 40 mA

Alarm:

160 mA

160 mA

Additional 5895XL
(Daisy-chained to this module)

(7 max.)

Standby:

10 mA

Alarm:

10 mA

Addressable Devices

(381 max.)

Standby:

0.55 mA

Alarm:

0.55 mA

5815XL SLC Expander

(2 max.)

Standby:

55 mA

mA

Alarm:

55 mA

mA

5860 Remote Fire Alarm Annunciator

(8 max.)

Standby:

20 mA

mA

Alarm:

25 mA

mA

5824 Serial / Parallel Module

(2 max.)

Standby:

45 mA

mA

Alarm:

45 mA

mA

5865-4 LED Annunciator

(with reset and silence switches)

(8 max.)

Standby:

35 mA

mA

Alarm:

145 mA

mA

5865-3 LED Annunciator

Standby:

35 mA

mA

Alarm:

145 mA

mA

5880 Generic LED Driver Module

Standby:

35 mA

mA

Alarm:

200 mA

mA

A

Total System Current

**Auxiliary Devices

Refer to devices manual for current rating.

Alarm/Standby:

mA

mA

mA

Alarm/Standby:

mA

mA

mA

Alarm/Standby:

mA

mA

mA

Alarm/Standby:

mA

mA

mA

B

Auxiliary Devices Current

Alarm:

mA

mA

Alarm:

mA

mA

Alarm:

mA

mA

Alarm:

mA

mA

C

Notification Appliances Current

mA

D

Total current ratings of all devices in system (line A + line B + C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A

F

Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):

H

G

Multiply lines E and F.

Total standby AH

AH

H

Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)

H

I

Multiply lines E and H.

Total alarm AH

AH

J

***Add lines G and I.

Total ampere hours required

AH