Reznor Q6SD Option - Installation - Elec Heating User Manual
Page 39

39
Q6SD SERIES (3 PHASE)
Unit
Blower
Setting
External Static Pressure Drop - inches water column
0.1
0.2
0.3
0.4
0.5
0.6
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
X36
Tap T1**
1150
25
1050
27
1000
28
950
30
850
33
780
36
Tap T2
1230
23
1190
24
1120
25
1080
26
1000
28
950
30
Tap T3*
1464
19
1394
20
1332
21
1272
22
1216
23
1143
25
Tap T4
1600
18
1500
19
1400
20
1300
22
1200
24
1050
27
Tap T5
1700
17
1650
17
1600
18
1565
18
1530
19
1480
19
X48
Tap T1*
1515
19
1450
20
1380
21
1350
21
1300
22
1250
23
Tap T2**
1580
18
1520
19
1460
19
1400
20
1360
21
1300
22
Tap T3
1740
16
1690
17
1650
17
1600
18
1540
18
1500
19
Tap T4
1960
15
1910
15
1840
15
1820
16
1780
16
1740
16
Tap T5
2090
14
2050
14
2010
14
1975
14
1940
15
1900
15
X60
Tap T1
1515
19
1450
20
1380
21
1350
21
1300
22
1250
23
Tap T2**
1580
18
1520
19
1460
19
1400
20
1360
21
1300
22
Tap T3*
1740
16
1690
17
1650
17
1600
18
1540
18
1500
19
Tap T4
1960
15
1910
15
1840
15
1820
16
1780
16
1740
16
Tap T5
2090
14
2050
14
2010
14
1975
14
1940
15
1900
15
NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set coling speed
** Denotes factory set electric heating speed
Table 40. Q6SD Series Blower Data - (3 Phase Models)