Electrical data – Reznor Q6SD Option - Installation - Elec Heating User Manual
Page 10

10
P5RD SERIES - 208/230V - SINGLE PHASE MODELS
MODEL
P5RD-
HEATER
KW
SINGLE CIRCUIT
MULTIPLE SUPPLY CIRCUIT OPTION
MCA
REC,
WIRE GAGE
(90° C CU)
MOP
CIRCUIT A
(C
ompressor
& F
an
)
CIRCUIT B
(B
lower
& H
eater
)
MCA
REC, WIRE GAGE
(90° C CU)
MOP
MCA
REC, WIRE GAGE
(90° C CU)
MOP
024K
0
18.5
12
30
-
-
-
-
-
-
5
26.8
10
30
-
-
-
-
-
-
8
41.3
8
45
-
-
-
-
-
-
10
51.8
8
60
-
-
-
-
-
-
030K
0
22.1
10
35
-
-
-
-
-
-
5
26.8
10
35
-
-
-
-
-
-
8
41.3
8
45
-
-
-
-
-
-
10
51.8
8
60
-
-
-
-
-
-
15
76.8
4
80
50
8
60
26.8
10
30
036K
0
26.5
10
45
-
-
-
-
-
-
5
27.6
10
45
-
-
-
-
-
-
8
42.2
8
45
-
-
-
-
-
-
10
52.6
8
60
-
-
-
-
-
-
15
77.6
4
80
50
8
60
27.6
10
30
042KA
0
31.9
8
50
-
-
-
-
-
-
5
31.9
8
50
-
-
-
-
-
-
8
41.1
8
50
-
-
-
-
-
-
10
51.5
8
60
-
-
-
-
-
-
15
76.5
4
80
51.5
8
60
25
10
30
20
101.5
3
110
51.5
8
60
50
8
60
048KA
0
34.9
8
50
-
-
-
-
-
-
5
34.9
8
50
-
-
-
-
-
-
8
41.1
8
50
-
-
-
-
-
-
10
51.8
8
60
-
-
-
-
-
-
15
76.8
4
80
51.8
8
60
25
10
30
20
101.8
3
110
51.8
8
60
50
8
60
NOTE: P5RD 2, 2.5 & 3 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on
different circuits when adding a heater kit.
Table 9. P5RD Electrical Data (2, 2.5, & 3 Ton Units)
P5RD SERIES - 208/230V - SINGLE PHASE MODELS
MODEL
P5RD-
HEATER
KW
SINGLE CIRCUIT
MULTIPLE SUPPLY CIRCUIT OPTION
MCA
REC,
WIRE GAGE
(90° C CU)
MOP
CIRCUIT A
(C
ompressor
, B
lower
, & F
an
)
CIRCUIT B
(H
eater
)
MCA
REC,
WIRE GAGE
(90° C CU)
MOP
MCA
REC,
WIRE GAGE
(90° C CU)
MOP
042K
0
32.9
8
50
-
-
-
-
-
-
5
32.9
8
50
-
-
-
-
-
-
8
41.1
8
50
-
-
-
-
-
-
10
51.5
8
60
-
-
-
-
-
-
15
76.5
4
80
51.5
8
60
25
10
30
20
101.5
3
110
51.5
8
60
50
8
60
048K
0
37.6
8
60
-
-
-
-
-
-
5
37.6
8
60
-
-
-
-
-
-
8
41.1
8
60
-
-
-
-
-
-
10
51.5
8
60
-
-
-
-
-
-
15
76.5
4
80
51.5
8
60
25
10
30
20
101.5
3
110
51.5
8
60
50
8
60
060K
0
44
8
70
-
-
-
-
-
-
5
44
8
70
-
-
-
-
-
-
8
44
8
70
-
-
-
-
-
-
10
51.5
8
70
-
-
-
-
-
-
15
76.5
4
80
51.5
8
70
25
10
30
20
101.5
3
110
51.5
8
70
50
8
60
Table 10. P5RD Electrical Data (3.5, 4, & 5 Ton Units)