Table 23. Q7RD Electrical Data (2, 2.5, 3, 3.5 4, & 5 Ton Units)
Q7RD SERIES - 208/230V - SINGLE PHASE MODELS
Model
Number
Q7RD-
Heater
kW
MCA
MOP
Circuit A
(Compressor, Blower & Fan)
Circuit B
(Heater Only)
Circuit C
(Heater Only)
MCA
MOP
MCA
MOP
MCA
MOP
024K
0
16.9
25
-
-
-
-
-
-
5
41.9
45
-
-
-
-
-
-
8
56.5
60
16.9
25
39.6
40
-
-
10
66.9
70
16.9
25
50
60
-
-
030K
0
17.5
25
-
-
-
-
-
-
5
42.5
45
-
-
-
-
-
-
8
57.1
60
17.5
25
39.6
40
-
-
10
67.5
70
17.5
25
50
60
-
-
15
92.5
100
42.5
45
50
60
-
-
036K
0
23.7
35
-
-
-
-
-
-
5
48.7
50
-
-
-
-
-
-
8
63.2
70
23.7
35
39.6
40
-
-
10
73.7
80
23.7
35
50
60
-
-
15
98.7
100
48.7
50
50
60
-
-
042K
0
29.3
45
-
-
-
-
-
-
5
54.3
60
-
-
-
-
-
-
8
68.9
70
29.3
45
39.6
40
-
-
10
79.3
80
29.3
45
50
60
-
-
15
104.3
110
54.3
60
50
60
-
-
20
129.3
150
-
-
-
-
-
-
20 (3 circuit)
-
-
29.3
45
50.0
60
50
60
048K
0
34.2
50
-
-
-
-
-
-
5
59.2
70
-
-
-
-
-
-
8
73.7
80
34.2
50
39.6
40
-
-
10
84.2
90
34.2
50
50
60
-
-
15
109.2
110
59.2
70
50
60
-
-
20
134.2
150
-
-
-
-
-
-
20 (3 circuit)
-
-
34.2
50
50
60
50
60
060K
0
39.9
50
-
-
-
-
-
-
5
64.9
70
-
-
-
-
-
-
8
79.5
80
39.9
50
39.6
40
-
-
10
89.9
90
39.9
50
50
60
-
-
15
114.9
125
64.9
70
50
60
-
-
20
139.9
150
-
-
-
-
-
-
20 (3 circuit)
-
-
39.9
50
50
60
50
60