Reznor Q6SD Option - Installation - Elec Heating User Manual
Page 12

12
P7RD SERIES - 208/230V - SINGLE PHASE MODELS
MODEL
P7RD-
HEATER
(KW)
SINGLE CIRCUIT
MULTIPLE SUPPLY CIRCUIT OPTION
MCA
REC, WIRE
GAGE
(90°C CU)
MOP
Circuit A (Compressor & Fan)
Circuit B (Blower & Heater)
MCA
REC, WIRE GAGE
(90°C CU)
MOP
MCA
REC, WIRE GAGE
(90°C CU)
MOP
024K
0
14.8
14
20
-
-
-
-
-
-
5
26.6
10
30
-
-
-
-
-
-
8
41.2
8
45
-
-
-
-
-
-
10
51.6
8
60
-
-
-
-
-
-
030K
0
16.3
12
25
-
-
-
-
-
-
5
26.6
10
30
-
-
-
-
-
-
8
41.2
8
45
-
-
-
-
-
-
10
51.6
8
60
-
-
-
-
-
-
15
76.6
4
80
50
8
60
26.6
10
30
036K
0
22.0
10
35
-
-
-
-
-
-
5
27.6
10
35
-
-
-
-
-
-
8
42.2
8
45
-
-
-
-
-
-
10
52.6
8
60
-
-
-
-
-
-
15
77.6
4
80
50
8
60
27.6
10
30
042K
0
29.6
10
45
-
-
-
-
-
-
5
29.6
10
45
8
43.5
8
45
10
53.9
8
60
15
78.9
4
80
50
8
60
28.9
10
30
20
103.9
3
110
50
8
60
53.9
8
60
048K
0
30.8
8
50
5
30.8
8
50
8
43.5
8
50
10
53.9
8
60
15
78.9
4
80
50
8
60
28.9
10
30
20
103.9
3
110
50
8
60
53.9
8
60
MODEL
P7RD-
HEATER
(KW)
Single
Circuit
MCA
Rec, Wire
Gage (90°C
Cu)
MOP
Multiple Supply Circuit Option
Circuit A (Compressor & Fan)
Circuit B (Blower & Heater)
MCA
Rec, Wire Gage
(90°C Cu)
MOP
MCA
Rec, Wire Gage
(90°C Cu)
MOP
024K*
0
14.5
14
20
-
-
-
-
-
-
5
26.6
10
30
-
-
-
-
-
-
8
41.2
8
45
-
-
-
-
-
-
10
51.6
8
60
-
-
-
-
-
-
030K*
0
15.1
12
25
-
-
-
-
-
-
5
26.6
10
30
-
-
-
-
-
-
8
41.2
8
45
10
51.6
8
60
15
76.6
4
80
50
8
60
26.6
10
30
*NOTE: Compressors changed for these models. MCA changed for the units with no heater kits, MOP did not change.
Table 13. P7RD Electrical Data (2, 2.5, 3, 3.5, & 4 Ton Units)