Q6SD SERIES (SINGLE PHASE)
UNIT
BLOWER
SETTING
External Static Pressure Drop - inches water column
0.1
0.2
0.3
0.4
0.5
0.6
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
CFM
HEAT
RISE
X24
Tap T1*
1110
28
869
36
529
60
Tap T2**
1211
26
996
32
700
45
609
52
Tap T3
1400
23
1350
23
1200
26
1150
27
1080
29
1030
31
Tap T4
1600
20
1500
21
1400
23
1300
24
1200
26
1050
30
Tap T5
1700
19
1650
19
1600
20
1565
20
1530
21
1480
21
X30
Tap T1**
1211
26
996
32
700
45
609
52
Tap T2*
1275
25
1077
29
940
34
876
36
807
39
732
43
Tap T3
1400
23
1350
23
1200
26
1150
27
1080
29
1030
31
Tap T4
1600
20
1500
21
1400
23
1300
24
1200
26
1050
30
Tap T5
1700
19
1650
19
1600
20
1565
20
1530
21
1480
21
X36
Tap T1**
1150
27
1050
30
1000
32
950
33
850
37
780
41
Tap T2
1230
26
1190
27
1120
28
1080
29
1000
32
950
33
Tap T3*
1464
22
1394
23
1332
24
1272
25
1216
26
1143
28
Tap T4
1600
20
1500
21
1400
23
1300
24
1200
26
1050
30
Tap T5
1700
19
1650
19
1600
20
1565
20
1530
21
1480
21
X42
Tap T1**
1150
27
1050
30
1000
32
950
33
850
37
780
41
Tap T2
1230
26
1190
27
1120
28
1080
29
1000
32
950
33
Tap T3
1400
23
1350
23
1200
26
1150
27
1080
29
1030
31
Tap T4*
1524
21
1476
21
1424
22
1379
23
1329
24
1268
25
Tap T5
1700
19
1650
19
1600
20
1565
20
1530
21
1480
21
X48
Tap T1*
1515
21
1450
22
1380
23
1350
23
1300
24
1250
25
Tap T2**
1580
20
1520
21
1460
22
1400
23
1360
23
1300
24
Tap T3
1740
18
1690
19
1650
19
1600
20
1540
21
1500
21
Tap T4
1960
16
1910
17
1840
17
1820
17
1780
18
1740
18
Tap T5
2090
15
2050
15
2010
16
1975
16
1940
16
1900
17
X60
Tap T1
1515
21
1450
22
1380
23
1350
23
1300
24
1250
25
Tap T2**
1580
20
1520
21
1460
22
1400
23
1360
23
1300
24
Tap T3*
1740
18
1690
19
1650
19
1600
20
1540
21
1500
21
Tap T4
1960
16
1910
17
1840
17
1820
17
1780
18
1740
18
Tap T5
2090
15
2050
15
2010
16
1975
16
1940
16
1900
17
NOTES:
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set coling speed
** Denotes factory set electric heating speed
Table 39. Q6SD Series Blower Data - (Single Phase Models)