Table 31. P7RD-A Series Blower Data

P7RD-A Series Blower Curves

UNIT

BLOWER
SETTING

External Static Pressure Drop - inches water column

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM

HEAT

RISE

CFM

HEAT

RISE

CFM

HEAT

RISE

CFM

HEAT

RISE

CFM

HEAT

RISE

CFM

HEAT

RISE

CFM

HEAT

RISE

CFM

HEAT

RISE

024KA

Tap T1*

840

38

800

39

755

42

710

44

650

49

600

53

550

57

505

63

Tap T2

1010

31

965

33

925

34

885

36

845

37

790

40

735

43

690

46

Tap T3**

1115

28

1080

29

1040

30

1000

32

965

33

925

34

875

36

820

39

Tap T4

1205

26

1170

27

1130

28

1095

29

1055

30

1020

31

985

32

940

34

Tap T5

1335

24

1300

24

1270

25

1230

26

1195

26

1160

27

1125

28

1090

29

030KA

Tap T1

840

38

800

39

755

42

710

44

650

49

600

53

550

57

505

63

Tap T2*

1010

31

965

33

925

34

885

36

845

37

790

40

735

43

690

46

Tap T3**

1115

28

1080

29

1040

30

1000

32

965

33

925

34

875

36

820

39

Tap T4

1205

26

1170

27

1130

28

1095

29

1055

30

1020

31

985

32

940

34

Tap T5

1335

24

1300

24

1270

25

1230

26

1195

26

1160

27

1125

28

1090

29

036KA

Tap T1

905

35

865

37

810

39

755

42

695

45

645

49

590

54

555

57

Tap T2

1130

28

1090

29

1050

30

1000

32

950

33

895

35

835

38

790

40

Tap T3*

1265

25

1225

26

1190

27

1145

28

1100

29

1045

30

995

32

940

34

Tap T4**

1380

23

1340

24

1305

24

1270

25

1225

26

1180

27

1130

28

1080

29

Tap T5

1540

21

1510

21

1475

21

1440

22

1405

22

1360

23

1320

24

1270

25

042KA

Tap T1*

1375

23

1345

23

1310

24

1275

25

1240

25

1205

26

1160

27

1120

28

Tap T2**

1470

21

1435

22

1400

23

1370

23

1335

24

1300

24

1260

25

1215

26

Tap T3

1600

20

1570

20

1535

21

1505

21

1470

21

1440

22

1400

23

1355

23

Tap T4

1715

18

1680

19

1650

19

1620

20

1585

20

1545

20

1505

21

1470

21

Tap T5

1895

17

1865

17

1830

17

1795

18

1760

18

1730

18

1695

19

1655

19

048KA

Tap T1**

1375

23

1345

23

1310

24

1275

25

1240

25

1205

26

1160

27

1120

28

Tap T2

1470

21

1435

22

1400

23

1370

23

1335

24

1300

24

1260

25

1215

26

Tap T3*

1600

20

1570

20

1535

21

1505

21

1470

21

1440

22

1400

23

1355

23

Tap T4

1715

18

1680

19

1650

19

1620

20

1585

20

1545

20

1505

21

1470

21

Tap T5

1895

17

1865

17

1830

17

1795

18

1760

18

1730

18

1695

19

1655

19

060KA

Tap T1**

1290

24

1255

25

1220

26

1185

27

1145

28

1110

28

1070

30

1035

31

Tap T2

1645

19

1615

20

1580

20

1550

20

1520

21

1490

21

1440

22

1405

22

Tap T3*

1885

17

1855

17

1820

17

1785

18

1755

18

1720

18

1685

19

1650

19

Tap T4

2020

16

1985

16

1955

16

1920

16

1890

17

1850

17

1820

17

1785

18

Tap T5

2185

14

2170

15

2160

15

2145

15

2130

15

2090

15

2055

15

2015

16

NOTES:

Calculated values in matrix are all with 10KW for 1 phase
Temperature rises shaded gray are for reference only. These conditions are not recommended.
* Denotes factory set cooling speed
** Denotes factory set electric heating speed

This manual is related to the following products: