Q5RD SERIES - 208/230V - SINGLE PHASE MODELS

MODEL

Q5RD-

HEATER

KW

MCA

REC, WIRE

GAGE

(90° C CU)

MOP

CIRCUIT A

(C

ompressor

& B

lower

)

CIRCUIT B

(F

an

& H

eater

)

CIRCUIT C

(H

eater

o

nly

)

MCA

REC, WIRE

GAGE (90° C CU)

MOP

MCA

REC, WIRE

GAGE (90° C CU)

MOP

MCA

REC, WIRE

GAGE (90° C CU)

MOP

024K

0

18.1

12

30

-

-

-

-

-

-

-

-

-

5

43.1

8

50

-

-

-

-

-

-

-

-

-

8

57.7

6

60

-

-

-

-

-

-

-

-

-

10

68.1

6

70

17.1

12

25

51

8

60

-

-

-

030K

0

22.2

10

35

-

-

-

-

-

-

-

-

-

5

47.2

8

50

-

-

-

-

-

-

-

-

-

8

61.8

6

70

20.8

10

35

41

8

45

-

-

-

10

72.2

6

80

20.8

10

35

51.4

8

60

-

-

-

15

97.2

3

100

45.8

8

50

51.4

8

60

-

-

-

036KA

0

26.5

10

45

-

-

-

-

-

-

-

-

-

5

51.5

8

60

-

-

-

-

-

-

-

-

-

8

66

6

70

25.4

10

40

40.7

8

45

-

-

-

10

76.5

4

80

25.4

10

40

51.1

8

60

-

-

-

15

101.5

3

110

50.4

8

60

51.1

8

60

-

-

-

048KA

0

34.9

8

50

-

-

-

-

-

-

-

-

-

5

59.9

6

70

33.5

8

50

26.5

10

30

-

-

-

8

74.5

6

90

33.5

8

50

41

8

45

-

-

-

10

84.9

4

90

33.5

8

50

51.5

8

60

-

-

-

15

109.9

3

110

58.5

6

70

51.5

8

60

-

-

-

20

134.9

1

150

-

-

-

-

-

-

-

-

-

20 (3 cir.)

-

-

-

33.5

8

50

51.5

8

60

50

8

60

Table 19. Q5RD w/ PSC Indoor Motor Electrical Data (2 & 2.5 Ton Units)

Q5RD SERIES - 208/230V - SINGLE PHASE MODELS

MODEL

NUMBER

Q5RD

HEATER

KW

MCA

REC, WIRE

GAGE

(90° C CU)

MOP

CIRCUIT A

(C

ompressor

, B

lower

& F

an

)

CIRCUIT B

(H

eater

o

nly

)

CIRCUIT C

(H

eater

o

nly

)

MCA

REC, WIRE

GAGE

(90° C C

u

)

MOP

MCA

REC, WIRE

GAGE

(90° C C

u

)

MOP MCA

REC, WIRE

GAGE

(90° C C

u

)

MOP

036K

0

28.5

10

45

-

-

-

-

-

-

-

-

-

5

53.5

8

60

-

-

-

-

-

-

-

-

-

8

68

6

70

28.5

10

45

39.6

8

40

-

-

-

10

78.5

4

80

28.5

10

45

50

8

60

-

-

-

15

103.5

3

110

53.5

8

60

50

8

60

-

-

-

042K

0

32.2

8

50

-

-

-

-

-

-

-

-

-

5

57.2

6

70

-

-

-

-

-

-

-

-

-

8

71.8

6

80

32.2

8

50

39.6

8

40

-

-

-

10

82.2

4

90

32.2

8

50

50

8

60

-

-

-

15

107.2

3

110

57.2

6

70

50

8

60

-

-

-

20

132.2

1

150

-

-

-

-

-

-

-

-

-

20 (3 circuit)

-

-

-

32.2

8

50

50

8

60

50

8

60

048K

0

37.6

8

60

-

-

-

-

-

-

-

-

-

5

62.6

6

80

37.6

8

60

25

10

30

-

-

-

8

77.2

4

90

37.6

8

60

39.6

8

40

-

-

-

10

87.6

4

100

37.6

8

60

50

8

60

-

-

-

15

112.6

2

125

62.6

6

80

50

8

60

-

-

-

20

137.6

1

150

-

-

-

-

-

-

-

-

-

20 (3 circuit)

-

-

-

37.6

8

60

50

8

60

50

8

60

060K

0

40.5

8

60

-

-

-

-

-

-

-

-

-

5

65.5

6

80

40.5

8

60

25

10

30

-

-

-

8

80.1

4

90

40.5

8

60

39.6

8

40

-

-

-

10

90.5

4

100

40.5

8

60

50

8

60

-

-

-

15

115.5

2

125

65.5

6

80

50

8

60

-

-

-

20

140.5

1

150

-

-

-

-

-

-

-

-

-

20 (3 circuit)

-

-

-

40.5

8

60

50

8

60

50

8

60

Table 20. Q5RD w/ ECM Indoor Motor Electrical Data (3, 3.5, 4, & 5 Ton Units)

This manual is related to the following products: