16
Q5RD SERIES - 208/230V - SINGLE PHASE MODELS
MODEL
Q5RD-
HEATER
KW
MCA
REC, WIRE
GAGE
(90° C CU)
MOP
CIRCUIT A
(C
ompressor
& B
lower
)
CIRCUIT B
(F
an
& H
eater
)
CIRCUIT C
(H
eater
o
nly
)
MCA
REC, WIRE
GAGE (90° C CU)
MOP
MCA
REC, WIRE
GAGE (90° C CU)
MOP
MCA
REC, WIRE
GAGE (90° C CU)
MOP
024K
0
18.1
12
30
-
-
-
-
-
-
-
-
-
5
43.1
8
50
-
-
-
-
-
-
-
-
-
8
57.7
6
60
-
-
-
-
-
-
-
-
-
10
68.1
6
70
17.1
12
25
51
8
60
-
-
-
030K
0
22.2
10
35
-
-
-
-
-
-
-
-
-
5
47.2
8
50
-
-
-
-
-
-
-
-
-
8
61.8
6
70
20.8
10
35
41
8
45
-
-
-
10
72.2
6
80
20.8
10
35
51.4
8
60
-
-
-
15
97.2
3
100
45.8
8
50
51.4
8
60
-
-
-
036KA
0
26.5
10
45
-
-
-
-
-
-
-
-
-
5
51.5
8
60
-
-
-
-
-
-
-
-
-
8
66
6
70
25.4
10
40
40.7
8
45
-
-
-
10
76.5
4
80
25.4
10
40
51.1
8
60
-
-
-
15
101.5
3
110
50.4
8
60
51.1
8
60
-
-
-
048KA
0
34.9
8
50
-
-
-
-
-
-
-
-
-
5
59.9
6
70
33.5
8
50
26.5
10
30
-
-
-
8
74.5
6
90
33.5
8
50
41
8
45
-
-
-
10
84.9
4
90
33.5
8
50
51.5
8
60
-
-
-
15
109.9
3
110
58.5
6
70
51.5
8
60
-
-
-
20
134.9
1
150
-
-
-
-
-
-
-
-
-
20 (3 cir.)
-
-
-
33.5
8
50
51.5
8
60
50
8
60
Table 19. Q5RD w/ PSC Indoor Motor Electrical Data (2 & 2.5 Ton Units)
Q5RD SERIES - 208/230V - SINGLE PHASE MODELS
MODEL
NUMBER
Q5RD
HEATER
KW
MCA
REC, WIRE
GAGE
(90° C CU)
MOP
CIRCUIT A
(C
ompressor
, B
lower
& F
an
)
CIRCUIT B
(H
eater
o
nly
)
CIRCUIT C
(H
eater
o
nly
)
MCA
REC, WIRE
GAGE
(90° C C
u
)
MOP
MCA
REC, WIRE
GAGE
(90° C C
u
)
MOP MCA
REC, WIRE
GAGE
(90° C C
u
)
MOP
036K
0
28.5
10
45
-
-
-
-
-
-
-
-
-
5
53.5
8
60
-
-
-
-
-
-
-
-
-
8
68
6
70
28.5
10
45
39.6
8
40
-
-
-
10
78.5
4
80
28.5
10
45
50
8
60
-
-
-
15
103.5
3
110
53.5
8
60
50
8
60
-
-
-
042K
0
32.2
8
50
-
-
-
-
-
-
-
-
-
5
57.2
6
70
-
-
-
-
-
-
-
-
-
8
71.8
6
80
32.2
8
50
39.6
8
40
-
-
-
10
82.2
4
90
32.2
8
50
50
8
60
-
-
-
15
107.2
3
110
57.2
6
70
50
8
60
-
-
-
20
132.2
1
150
-
-
-
-
-
-
-
-
-
20 (3 circuit)
-
-
-
32.2
8
50
50
8
60
50
8
60
048K
0
37.6
8
60
-
-
-
-
-
-
-
-
-
5
62.6
6
80
37.6
8
60
25
10
30
-
-
-
8
77.2
4
90
37.6
8
60
39.6
8
40
-
-
-
10
87.6
4
100
37.6
8
60
50
8
60
-
-
-
15
112.6
2
125
62.6
6
80
50
8
60
-
-
-
20
137.6
1
150
-
-
-
-
-
-
-
-
-
20 (3 circuit)
-
-
-
37.6
8
60
50
8
60
50
8
60
060K
0
40.5
8
60
-
-
-
-
-
-
-
-
-
5
65.5
6
80
40.5
8
60
25
10
30
-
-
-
8
80.1
4
90
40.5
8
60
39.6
8
40
-
-
-
10
90.5
4
100
40.5
8
60
50
8
60
-
-
-
15
115.5
2
125
65.5
6
80
50
8
60
-
-
-
20
140.5
1
150
-
-
-
-
-
-
-
-
-
20 (3 circuit)
-
-
-
40.5
8
60
50
8
60
50
8
60
Table 20. Q5RD w/ ECM Indoor Motor Electrical Data (3, 3.5, 4, & 5 Ton Units)