Table 11. Heating Rise / Range
uNIt MoDEl
NuMBER
GaS
tYPE
HEatING
INPut
HEatING
outPut
HEatING RISE
RANGE (º F)
cFM RaNGE
(RISE ºF)*
4400
4600
4800
5000
5200
R6GN-150(C,D)-180C
LP
153,000
122,000
20 - 50
26
25
24
23
22
NAT.
180,000
144,000
20 - 50
30
29
28
27
26
R6GN-150(C,D)-270C
LP
230,000
184,000
30 - 60
39
37
35
34
33
NAT.
270,000
216,000
30 - 60
45
43
42
40
38
uNIt MoDEl
NuMBER
GaS
tYPE
HEatING
INPut
HEatING
outPut
HEatING RISE
RANGE (º F)
cFM RaNGE
(RISE ºF)*
5200
5400
5600
5800
6000
R6GN-180(C,D)-270C
LP
230,000
184,000
30 - 60
33
32
30
29
28
NAT.
270,000
216,000
30 - 60
38
37
36
34
33
R6GN-180(C,D)-315C
LP
268,000
214,000
30 - 60
38
37
35
34
33
NAT.
315,000
252,000
30 - 60
45
43
42
40
39
NOTE: * Rise (º F) = Heating Output ÷ CFM ÷ 1.08
NatuRal GaS
uNIt MoDEl
NuMBER
GaS
tYPE
HEatING
INPut
(BTU/HR.)
NuMBER
oF
BuRNERS
0 to
2,000 FT
2,000 to
4,000 FT
4,000 to
6,000 FT
6,000 to
7,000 FT
ElEVatIoN
661118
918839
918840
918841
NoRDYNE PaRt No.
R6GN-150(C,D)-180C
NAT.
180,000
4
1/8”
31
33
34
oRIFIcE SIZE
R6GN-150(C,D)-270C
NAT.
270,000
6
1/8”
31
33
34
R6GN-180(C,D)-315C
NAT.
315,000
7
1/8”
31
33
34
Table 9. Orifice or Drill Size for Natural Gas
Table 10. Orifice or Drill Size for Propane (LP) Gas
PROPANE (LP) GAS
uNIt MoDEl
NuMBER
GaS
tYPE
HEatING
INPut
(BTU/HR.)
NuMBER
oF
BuRNERS
0 to
2,000 FT
2,000 to
4,000 FT
4,000 to
6,000 FT
6,000 to
7,000 FT
ElEVatIoN
918798
918798
918798
918798
NoRDYNE PaRt No.
R6GN-150(C,D)-180C
LP
153,000
4
49
50
51
51
oRIFIcE SIZE
R6GN-180(C,D)-270C
LP
230,000
6
49
50
51
51
R6GN-180(C,D)-315C
LP
268,000
7
49
50
51
51