beautypg.com

Warning, Caution – Reznor R6GN Unit Installation Manual User Manual

Page 20

background image

20

Routine Maintenance

Please consult your dealer for maintenance information

and availability of maintenance contracts.At a minimum,

routine maintenance should include the following items:

WaRNING:

Never operate the unit without filters in place.
Dust and lint in the return air can build up
on internal components, resulting in loss of
efficiency, equipment damage, and possible fire.

• Inspect the condensate drain and outdoor coil at the

beginning of each cooling season. Remove any debris.

Clean the outdoor coil and louvers as necessary using

a mild detergent and water. Rinse thoroughly with water.

• The blower compartment should be cleaned monthly

during the heating and cooling seasons to remove any dirt

and lint that may have accumulated in the compartment

or on the blower and motor. Buildup of dirt and lint on

the blower and motor can create excessive loads on

the motor resulting in higher than normal operating

temperatures and possible shortened service life.

• It is recommended that the air filters be inspected and

cleaned or replaced every 3 to 4 weeks using filters of

like size and kind. Table 1 (page 8) lists the correct filter

sizes and quantities for each unit.

• Inspect the electrical connections for tightness at the

beginning of each heating and cooling season.

• Inspect and clean the screen of the vent cover assembly

at the beginning of each heating and cooling season.

WaRNING:

Holes in the heat exchanger can cause products
of combustion to enter the structure. Replace
the heat exchanger if leaks are found. Failure
to prevent products of combustion from being
circulated into the occupied space can create
potentially hazardous conditions including
carbon monoxide poisoning that could result
in personal injury or death.

• Maintain heat exchanger and burners. The unit should

operate for many years without excessive scale buildup

in the heat exchanger, however, the heat exchanger, the

vent system, and the burners should be inspected and

cleaned (if required) by a qualified serviceman annually

to ensure continued safe operation. Particular attention

must be given to identify deterioration from corrosion
or other sources.

Motor / Bearing Lubrication Requirements

• The blower assembly in this unit is equipped with three

support bearings and one pillow block drive bearing. The

support bearings are sealed cartridge units and require

no further lubrication. The drive bearing is equipped for

future lubrication (field supplied fitting required) since

it is capable of more severe duty. The drive bearing

should be checked annually for lubrication requirements

based on application and operating conditions or as

maintenance experience dictates. Extreme care is

important to prevent overfilling or introduction of dirt

into the bearing.

• The indoor blower motor is pre-lubricated at the factory

and does not require additional lubrication under normal

application of this equipment. The motor is equipped with

grease fittings if you chose to re-lubricate the bearings

based on abnormal conditions or applications. Refer to

the motor manufacturers Installation, Operation, and

Maintenance Instructions supplied in the owners packet

for suggested amounts and type based on the bearing

model number listed on the motor nameplate.

• The combustion air blower motor and outdoor fan motors

are equipped with pre-lubricated sealed ball bearings.

No further oiling is required for the life of this product.

Cleaning the Burners

It is recommended that the burners be inspected and

cleaned annually (if required) by a qualified technician to

ensure continued safe operation. Particular attention must

be given to identify deterioration from corrosion or other

sources. If the burners must be cleaned, follow these steps:
1. Shut off the gas supply to the unit either at the meter

or at a manual valve in the supply piping.

IMPoRtaNt NotE! See gas valve label on the unit or

Figure 17 (page 35) for proper gas shutdown instructions.

2. Turn off all power to the unit and set the thermostat to

the lowest temperature setting.

3. Remove the louvered access panel from the unit.
4. Turn the gas control knob to the “OFF” position.

cautIoN:

Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.

5. Disconnect the wires from the gas valve, ignitor, flame

sensor, and rollout switch.

6. Using two wrenches, separate the ground-joint union

in the gas supply piping at the unit.

7. Remove the piping between the gas valve and the

ground-joint union.

8. Remove four screws securing the burner assembly to

the unit.

9. Carefully remove the burner assembly from the unit.

Do Not DaMaGE tHE IGNItoR WHIlE REMoVING

tHE BuRNER aSSEMBlY.

10. Inspect the burners for accumulated dust or debris.

If necessary, carefully clean them with a soft wire

brush and/or the nozzle of a vacuum cleaner.

Do

Not DaMaGE tHE IGNItoR oR FlaME SENSoR

WHIlE clEaNING tHE BuRNER.

11. Replace all the parts in reverse order from which they

were removed.