beautypg.com

Caution, Warning – Reznor R6GN Unit Installation Manual User Manual

Page 18

background image

18

blowers should continue to run when the over-temperature

limit control switch opens.
3. Remove the close-off plate immediately after the over-

temperature limit control opens. If the unit operates
for more than four minutes with no return air, set the
thermostat below room temperature, shut off power to
the unit, and replace the over-temperature limit control.

NotE: On some low static/high airflow applications, the

Over-Temperature limit control may not function. To ensure

the limit is functioning properly, the outlet may also have to

be slightly restricted to achieve higher outlet temperatures

.

Verifying & Adjusting Firing Rate

The firing rate must be verified for each installation to

prevent over-firing of the unit.

cautIoN:

Do not re-drill the burner orifices. If the orifice
size must be changed, use only new orifices.

IMPoRtaNt NotE: The firing rate must not exceed the

rate shown on the unit data label. At altitudes above 2,000

ft., it must not exceed that on the data label less 4% for

each 1,000 ft.
Follow the steps below to determine the unit firing rate:
• For installations at 2,000 feet and less, the firing rate is

the same as shown on the unit rating label.

• For installations above 2,000 feet, compute the correct

firing rate as shown in the example on page 13.

1. Obtain the gas heating value from the gas supplier

(HHV).

2. Shut off all other gas fired appliances.
3. Start the unit in heating mode and allow it to run for at

least three minutes.

4. Measure the time (in seconds) required for the gas

meter to complete one revolution.

5. Convert the time per revolution to cubic feet of gas per

hour using Table 7 (page 33).

6. Multiply the gas flow rate in cubic feet per hour by the

heating value of the gas in Btu per cubic foot to obtain
the firing rate in Btu per hour. See example:

Manifold Pressure Adjustment
The manifold pressure must be set to the appropriate
value for your installation. To adjust the manifold pressure:
1. Obtain the required manifold pressure setting. Refer to

either Table 9 for natural gas or Table 10 for LP/propane
gas (page 34).

NotE: The values listed in the tables

are based on sea level values. At higher altitudes, the
heating value of gas is lower than the sea level heating
value.

2. Remove the regulator cap. Turn the high fire

adjusting screw clockwise to increase the pressure or
counterclockwise to reduce the pressure.

3. Replace the regulator cap after adjustments are

complete.

Refrigerant charging

WaRNING:

If repairs make it necessary for evacuation and
charging, it should only be done by qualified,
trained personnel thoroughly familiar with this
equipment. Some local codes require licensed
installation/service personnel to service this
type of equipment. Under no circumstances
should the owner attempt to install and/or
service this equipment.

Failure to comply with this warning could result
in property damage, personal injury, or death.

This Single Package Gas Heating / Electric Cooling unit

is fully charged at the factory and requires no charging

when installed accordingly. Units should be operating

with liquid sub-cooling readings between 13° F - 15° F.

If measurements indicate a lower or higher sub-cooling

reading, refrigerant levels must be adjusted to achieve

maximum system performance. The refrigerant charge

can be checked and adjusted through the service ports

located behind the service panel. Use only gauge lines

which have a “Schrader” depression device to actuate

the valve.
Refrigerant charging charts for 12.5 and 15 ton units

are included in these instructions. To identify proper unit

charge operation see Figure 13 (page 28) for 12.5 ton or

Figure 14 (page 29) for 15 ton.

NotE: Both refrigeration

stages must be operating when taking liquid temperature

and pressure measurements.
Refrigerant charging must be done by qualified personnel

familiar with safe and environmentally responsible

refrigerant handling procedures. See Unit Rating Plate

for proper amount of refrigerant.

Example:

• Time for 1 revolution of a gas meter with a 1 cubic

foot dial = 40 seconds.

• From Table 7, read 90 cubic feet gas per hour.
• Local heating value of the gas (obtained from gas

supplier) = 1,040 Btu per cubic foot.

• Input rate = 1,040 x 90 = 93,600 Btuh.

7. Adjustments to the firing rate can be made by adjusting

the gas manifold pressure. See the High Altitude Deration
section (pages 12 - 13) for additional information of
firing rate at elevations above 2000 ft.