Carrier 19XRV User Manual
Page 38

38
APPENDIX B — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION
CCN
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
System Cooling Demand
Level
N/A
R
N/A
N/A
N/A
AV:9006
cool_demand_level_1
System Demand Limiting
N/A
R
N/A
N/A
OFF/ON
BV:3
dem_lmt_act_1
Target Guide Vane Position
GV_TRG
R
%
N/A
0 to 100
AV:41
gv_trg_1
Target VFD Speed
VFD_OUT
R
%
N/A
0 to 100
AV:42
vfd_out_1
Tower Fan Relay High
TFR_HIGH
R
N/A
OFF
OFF/ON
BV:13
tfr_high_1
Tower Fan Relay Low
TFR_LOW
R
N/A
OFF
OFF/ON
BV:14
tfr_low_1
User Defined Analog 1
N/A
R
N/A
N/A
N/A
AV:2901
user_analog_1_1
User Defined Analog 2
N/A
R
N/A
N/A
N/A
AV:2902
user_analog_2_1
User Defined Analog 3
N/A
R
N/A
N/A
N/A
AV:2903
user_analog_3_1
User Defined Analog 4
N/A
R
N/A
N/A
N/A
AV:2904
user_analog_4_1
User Defined Analog 5
N/A
R
N/A
N/A
N/A
AV:2905
user_analog_5_1
User Defined Binary 1
N/A
R
N/A
N/A
N/A
BV:2911
user_binary_1_1
User Defined Binary 2
N/A
R
N/A
N/A
N/A
BV:2912
user_binary_2_1
User Defined Binary 3
N/A
R
N/A
N/A
N/A
BV:2913
user_binary_3_1
User Defined Binary 4
N/A
R
N/A
N/A
N/A
BV:2914
user_binary_4_1
User Defined Binary 5
N/A
R
N/A
N/A
N/A
BV:2915
user_binary_5_1
CHW
— Chilled Water
R
— Read
VFD
— Variable Frequency Drive
W