Table 6

Powerflex 755 Fault Code Descriptions and Corrective Actions

VFD

FAULT

CODE

ON VFD

HIST

SCREEN

ICVC

FAULT
STATE

FAULT TYPE

DESCRIPTION

CORRECTIVE ACTION

NONE

206

Processor memory fault

Consult VFD manual to resolve generic fault.

0

No Entry

2

207

Auxiliary Input

Input is open.

Check Compressor Discharge High Pressure
switch wiring and accuracy.
Check for high condenser water temperatures,
low water flow, fouled tubes.
Check for division plate/gasket bypass. Check for
noncondensables in refrigerant.

3

210

Power Loss

Line voltage dropout

Temporary loss of voltage. Disable Single Cycle
Dropout in VFD_CONF sceen.

4

215

Undervoltage

Low DC bus voltage

Verify phase-to-phase and phase-to-ground line
voltage. VFD Circuit Board malfunction.
Call Carrier Service.

5

166

Overvoltage

High DC bus voltage

Verify phase to phase and phase to ground line
voltage. Monitor AC line for high transient voltage
conditions.

7

217

Motor Overload

An internal electronic overload trip has occurred.

Any phase current > 106% RLA. Can result from
significant load side current imbalance when
running at full load.
Check entering condenser water temperature
and water flow rate.
Check Motor Rated Load Amps in VFD_CONF
screen.

8

219

Heat Sink Over-
temp

Heat sink temperature has exceeded the maxi-
mum operating temperature

Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling orifice and refrig-
erant strainer.
Check for proper VFD cooling fan operation and
air flow blockage.

9

219

Transistor Over-
temp

The output transistors have exceeded the maxi-
mum operating temperature

Check that VFD refrigerant isolation valves are
open.
Check VFD refrigerant cooling orifice and refrig-
erant strainer.
Check for proper VFD cooling fan operation and
air flow blockage.

12

286

HW Overcurrent

The drive output current has exceeded the hard-
ware current limit.

Check for high entering water temperature or low
condenser water flow. Check current settings in
VFD_CONF screen.

13

220

Ground Fault

A current path to earth ground greater than 25%
of drive rating has occurred.

Check the motor, motor terminals, and external
wiring to the drive output terminals for a
grounded condition.

14

206

Ground Warning

The ground current has exceeded the level set in
P467

15

206

Load Loss

If this fault appears, there may be a problem with
software configuration.

To reset the processor, cycle power to chiller,
check ICVC VFD_CONF settings and save set-
tings when exiting VFD_CONF screen.
Check VFD parameters with Drive Explorer.

17

216

The DC bus ripple
has exceeded a
preset level.

Line Voltage imbalance

Check phase-to-phase and phase-to-ground dis-
tribution bus voltage. Increase Line Voltage %
Imbalance in VFD_CONF screen.

20

206

TorqPrv Spd Band

See VFD Fault Code 15

See VFD Fault Code 15

21

225

Output PhaseLoss

The current in one or more phases has been lost
or remains below a preset level.

Check Motor Current % Imbalance in
VFD_CONF screen.

24

204

Decel Inhibit

The drive is not following a commanded decelera-
tion because it is attempting to limit the bus volt-
age.

Verify input voltage is within drive specified limits.
Verify system ground impedance follows proper
grounding techniques.
Disable bus regulation P186 and/or add dynamic
brake resistor and/or extend deceleration time
P537 and P538.

33

206

AuRsts Exhausted

See VFD Fault Code 15

See VFD Fault Code 15

36

286

SW Overcurrent

The drive output current has exceeded the 1 ms
current rating.

Check for excess load, improper DC boost set-
ting, DC brake volts set too high.