Table 4 — ICVC Alert Codes

PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue. No reset is
necessary.

*[LIMIT] is shown on the ICVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is

the actual pressure, temperature, voltage, etc., at which the control tripped.

ICVC FAULT

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

100

PRESTART
ALERT

STARTS LIMIT
EXCEEDED

100

Excessive compressor starts

(8 in 12 hours).

Depress the RESET softkey if additional start
is required. Reassess start-up requirements.

101

PRESTART
ALERT

HIGH BEARING
TEMPERATURE

101

Comp Thrust Brg Temp [VALUE]

exceeded limit of [LIMIT]*.

Check oil heater for proper operation.
Check for low oil level, partially closed oil sup-
ply valves, clogged oil filters.
Check the sensor wiring and accuracy.
Check Comp Thrust Brg Alert setting in
SETUP1 screen.

102

PRESTART
ALERT

HIGH MOTOR
TEMPERATURE

102

Comp Motor Winding Temp

[VALUE] exceeded limit of [LIMIT]*.

Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation,
or restrictions.
Check for excessive starts within a short time
span.
Check Comp Motor Temperature Override
setting in SETUP1 screen.

103

PRESTART
ALERT

HIGH
DISCHARGE
TEMP

103

Comp Discharge Temp [VALUE]

exceeded limit of [LIMIT]*.

Allow discharge sensor to cool.
Check sensor wiring and accuracy.
Check for excessive starts.
Check Comp Discharge Alert setting in
SETUP1 screen.

104

PRESTART
ALERT

LOW
REFRIGERANT
TEMP

104

Evaporator Refrig Temp [VALUE]

exceeded limit of [LIMIT]*.

Check transducer wiring and accuracy.
Check for low chilled fluid supply
temperatures.
Check refrigerant charge.
Check Refrig Override Delta T in SETUP1
screen.

105

PRESTART
ALERT

LOW OIL
TEMPERATURE

105

Oil Sump Temp [VALUE]

exceeded limit of [LIMIT]*.

Check oil heater contactor/relay and power.
Check oil level and oil pump operation.

106

PRESTART
ALERT

HIGH
CONDENSER
PRESSURE

106

Condenser Pressure [VALUE]

exceeded limit of [LIMIT]*.

Check transducer wiring and accuracy.
Check for high condenser water
temperatures.
Check high condenser pressure switch wiring.

107

PRESTART
ALERT

LOW LINE
VOLTAGE

107

Percent Line Voltage [VALUE]

exceeded limit of [LIMIT]*.

Check voltage supply.
Check voltage transformers and switch gear.
Consult power utility if voltage is low.

108

PRESTART
ALERT

HIGH LINE
VOLTAGE

108

Percent Line Voltage [VALUE]

exceeded limit of [LIMIT]*.

Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.

109

PRESTART
ALERT

GUIDE VANE
CALIBRATION

109

Actual Guide Vane Pos

Calibration Required Before Startup.

Press STOP button on ICVC and perform
Guide Vane Calibration in Controls Test
screen.
Check guide vane actuator feedback
potentiometer.

110

PRESTART
ALERT

HIGH
RECTIFIER
TEMP

110

Rectifier Temperature [VALUE]

exceeded limit of [LIMIT]*.

Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.

111

PRESTART
ALERT

HIGH
INVERTER
TEMP

111

Inverter Temperature [VALUE]

exceeded limit of [LIMIT]*.

Check that VFD refrigerant isolation valves
are open.
Check VFD refrigerant cooling solenoid and
refrigerant strainer.
Check for proper VFD cooling fan operation
and blockage.