35

APPENDIX B

— OPTIONAL BACNET COMMUNICATIONS WIRING (cont)

Table D — Open System Wiring Specifications and Recommended Vendors

LEGEND

LOCAL ACCESS TO THE UPC OPEN CONTROL-

LER — The user can use a BACview

6

handheld keypad dis-

play unit or the Virtual BACview software as a local user inter-

face to an Open controller. These items let the user access the

controller network information. These are accessory items and

do not come with the UPC Open controller.

The BACview

6

unit connects to the local access port on the

UPC Open controller. See Fig. F. The BACview software must

be running on a laptop computer that is connected to the local

access port on the UPC Open controller. The laptop will re-

quire an additional USB link cable for connection.

See the BACview Installation and User Guide for instruc-

tions on connecting and using the BACview

6

device.

To order a BACview

6

Handheld (BV6H), consult Commer-

cial Products i-Vu

®

Open Control System Master Prices.

CONFIGURING THE UPC OPEN CONTROLLER'S

PROPERTIES — The UPC Open device and ComfortLink™

controls must be set to the same CCN Address (Element) num-

ber and CCN Bus number. The factory default settings for

CCN Element and CCN Bus number are 1 and 0 respectively.

If modifications to the default Element and Bus number are

required, both the ComfortLink and UPC Open configurations

must be changed.

The following configurations are used to set the CCN Ad-

dress and Bus number in the ComfortLink control. These con-

figurations can be changed using the scrolling marquee display

or accessory Navigator handheld device.

Configuration→CCN→CCN.A (CCN Address)
Configuration→CCN→CCN.B (CCN Bus Number)
The following configurations are used to set the CCN Ad-

dress and Bus Number in the UPC Open controller. These con-

figurations can be changed using the accessory BACview

6

dis-

play.

Navigation: BACview→CCN

Home: Element Comm Stat

Element: 1

Bus: 0
TROUBLESHOOTING — If there are problems wiring or

addressing the UPC Open controller, contact Carrier Technical

Support.

WIRING SPECIFICATIONS

RECOMMENDED VENDORS AND PART NUMBERS

Wire Type

Description

Connect Air

International

Belden

RMCORP

Contractors

Wire and Cable

MS/TP

Network (RS-485)

22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.

W221P-22227

25160PV

CLP0520LC

24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.

W241P-2000F

82841

25120-OR

Rnet

4 conductor, unshielded, CMP, 18 AWG, plenum rated.

W184C-2099BLB

6302UE

21450

CLP0442

AWG

American Wire Gage

CL2P

Class 2 Plenum Cable

CMP

Communications Plenum Rated

FEP

Fluorinated Ethylene Polymer

TC

Tinned Copper

Fig. F — BACview

6

Device Connection