beautypg.com

Carrier 19XRV User Manual

Page 13

background image

13

Table 4 — ICVC Alert Codes (cont)

CHILLER ALERTS

*[LIMIT] is shown on the ICVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or

alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control tripped.

ICVC FAULT

STATE

PRIMARY

MESSAGE

SECONDARY

MESSAGE

PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

140

SENSOR ALERT

LEAVING COND WATER
TEMP

140

Sensor Fault: Check

Leaving Cond Water Sensor.

Check sensor resistance or voltage drop.
Check for proper wiring.

141

SENSOR ALERT

ENTERING COND WATER
TEMP

141

Sensor Fault: Check

Entering Cond Water Sensor.

Check sensor resistance or voltage drop.
Check for proper wiring.

142

LOW OIL
PRESSURE ALERT

CHECK OIL FILTER

142

Low Oil Pressure Alert.

Check Oil Filter.

Check for partially or closed shut-off valves.
Check oil filter.
Check oil pump and power supply.
Check oil level.
Check for foaming oil at start-up.
Check transducer wiring and accuracy.

143

AUTORESTART
PENDING

LINE CURRENT
IMBALANCE

143

Line Current Imbal-

ance: Check VFD Fault His-
tory for Values.

Power loss has been detected in any phase.
Chiller automatically restarting.

144

AUTORESTART
PENDING

LINE VOLTAGE
DROP OUT

144

Single Cycle Line

Voltage Dropout.

A drop in line voltage has been detected within
2 voltage cycles.
Chiller automatically restarting if Auto Restart is
enabled in OPTIONS screen.

145

AUTORESTART
PENDING

HIGH LINE VOLTAGE

145

High Percent Line

Voltage [VALUE].

Check phase to phase and phase to ground line
power.

146

AUTORESTART
PENDING

LOW LINE VOLTAGE

146

Low Percent Line

Voltage [VALUE].

Check phase to phase and phase to ground line
power.

147

AUTORESTART
PENDING

VFD MODULE RESET

147->VFD Module Power-On
Reset When Running.

VFD Module has detected a hardware fault due
to electrical noise, power loss or software and
has reset. Chiller automatically restarting.
Check for power loss and sources of electro-
magnetic interference.

148

AUTORESTART
PENDING

POWER LOSS

148

Control Power-Loss

When Running.

Check 24 vac control power supply to ICVC.

149

SENSOR ALERT

HIGH DISCHARGE TEMP

149

Comp Discharge Temp

[VALUE] Exceeded Limit of
[LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring.
Check for proper inlet guide vane and optional
diffuser actuator operation.
Check for proper condenser flow and
temperature.
Check for high lift or low load.
Check for fouled tubes or noncondensables in
the chiller.

150

SENSOR ALERT

HIGH BEARING
TEMPERATURE

150

Comp Thrust Brg Temp

[VALUE] exceeded limit of
[LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring.
Check for partially closed service valves.
Check oil cooler TXV.
Check oil level and oil temperature.

151

CONDENSER
PRESSURE ALERT

PUMP RELAY
ENERGIZED

151

High Condenser Pres-

sure [VALUE]: Pump Ener-
gized to Reduce Pressure.

Check sensor wiring and accuracy.
Check condenser flow and water temperature.
Check for fouled tubes.
This alarm is not caused by the High Pressure
Switch.

152

RECYCLE ALERT

EXCESSIVE RECYCLE
STARTS

152

Excessive recycle

starts.

Chiller load is too low to keep compressor on
line and there has been more than 5 starts in
4 hours.
Increase chiller load, adjust hot gas bypass,
increase RECYCLE RESTART DELTA T from
SETUP1 Screen.

153

no message:
ALERT
only

no message; ALERT only

153

Lead/Lag Disabled-

Config: Duplicate Chiller
Address.

Illegal chiller address configuration in Lead/Lag
screen. Both chillers require a different address.

154

POTENTIAL
FREEZE-UP

COND PRESS/TEMP
TOO LOW

154

Condenser freeze up

prevention.

The condenser pressure transducer is reading a
pressure that could freeze the condenser tubes.
Check for condenser refrigerant leaks.
Check fluid temperature.
Check sensor wiring and accuracy.
Place the chiller in PUMPDOWN mode if the
vessel is evacuated.

155

OPTION SENSOR
FAULT

REMOTE RESET
SENSOR

155

Sensor Fault/Option

Disabled: Remote Reset
Sensor.

Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.

156

OPTION SENSOR
FAULT

AUTO CHILLED WATER
RESET

156

Sensor Fault/Option

Disabled: Auto Chilled Water
Reset.

Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J5.

157

OPTION SENSOR
FAULT

AUTO DEMAND LIMIT
INPUT

157

Sensor Fault/Option

Disabled: Auto Demand Limit
Input.

Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J5.

158

SENSOR ALERT

SPARE TEMPERATURE
#1

158

Spare Temperature 1

[VALUE] exceeded limit of
[LIMIT]*.

Check sensor resistance or voltage drop.
Check for proper wiring to CCM connector J4.
Check Spare Temp #1 Limit in SETUP1 screen.