Appendix b – Carrier 19XRV User Manual

Page 37

background image

37

APPENDIX B

— OPTIONAL BACNET COMMUNICATIONS WIRING (cont)

Table G — Network Points List

POINT DESCRIPTION

CCN

POINT NAME

READ/

WRITE

UNITS

DEFAULT

VALUE

RANGE

BACNET

OBJECT ID

BACNET

OBJECT NAME

1st Current Alarm State

ALARM_01

R

N/A

0-270

AV:4

alarm_01_1

Active Demand Limit

DEM_LIM

R/W

%

N/A

40 to 100

AV:6

dem_lim_1

Actual Guide Vane Position

GV_POS

R

%

N/A

0 to 100

AV:7

gv_pos_1

Actual VFD Speed

VFD_ACT

R

%

N/A

0 to 110

AV:11

vfd_act_1

Calc Evap Sat Temp

EAT

R

°F

N/A

-40 to 245

AV:13

ert_1

Chilled Water Deadband

CWDB

R

^F

1.0

0.5 to 2.0

AV:14

cwdb_1

Chilled Water Delta P

CHWPD

R

^F

N/A

-6.7 to 420

AV:15

chwpd_1

Chilled Water Delta T

CHW_DT

R

^F

N/A

-40 to 245

AV:16

chw_dt_1

Chilled Water Pump

CHLP

R

N/A

OFF

OFF/ON

BV:4

chlp_1

Chilled Water Temp

CHW_TMP

R

°F

N/A

-40 to 245

AV:17

chw_tmp_1

Chiller Start/Stop

CHIL_S_S

R/W

N/A

STOP

STOP/START

BV:5

chil_s_s_1

Comp Discharge Temp

CMPD

R

°F

N/A

-40 to 245

AV:18

cmpd_1

Comp Motor Winding Temp

MTRW

R

°F

N/A

-40 to 245

AV:19

mtrw_1

Comp Thrust Brg Temp

MTRB

R

°F

N/A

-40 to 245

AV:20

mtrb_1

Cond Water Flow

CDW_FLOW

R

N/A

NO

NO/YES

BV:6

cdw_flow_1

Cond Water Pump

CDP

R

N/A

OFF

OFF/ON

BV:7

cdp_1

Condenser Pressure

CRP

R

PSI

N/A

-6.7 to 420

AV:21

crp_1

Condenser Refrig Temp

CRT

R

°F

N/A

-40 to 245

AV:22

crt_1

Condenser Water Delta P

CDWPD

R

PSI

N/A

-6.7 to 420

AV:23

cdwpd_1

Control Point

LCW_STPT

R/W

°F

N/A

10 to 120

AV:24

lcw_stpt_1

Current CHW Setpoint

CHWSTPT

R

°F

N/A

0.00 to 99.9

AV:25

chwstpt_1

Demand Level 1

N/A

R

%

N/A

0 to 100

AV:1

dmv_lvl_1_perct_1

Demand Level 2

N/A

R

%

N/A

0 to 100

AV:2

dmv_lvl_2_perct_1

Demand Level 3

N/A

R

%

N/A

0 to 100

AV:3

dmv_lvl_3_perct_1

Element Comm Status

N/A

R

N/A

N/A

No Comm/Normal

BV:2999

element_stat_1

Element Communications
Alarm

N/A

R

N/A

N/A

Inactive/Active

BV:20

comm_lost_alm_1

Emergency Stop

EMSTOP

R

N/A

ENABLE

ENABLE/
EMSTOP

BV:8

emstop_1

Entering Chilled Water

ECW

R

°F

N/A

-40 to 245

AV:26

ecw_1

Entering Condenser Water

ECDW

R

°F

N/A

-40 to 245

AV:27

ecdw_1

Equipment Alarm

N/A

R

N/A

N/A

Comm Normal

Comm Lost

BV:1

element_alarm_1

Evaporator Pressure

ERP

R

PSI

N/A

-6.7 to 420

AV:28

erp_1

Evaporator Refrigerant Temp

ERT

R

°F

N/A

-40 to 245

AV:13

ert_1

Leaving Chilled Water -
Prime Variable

LCW

R

°F

N/A

-40 to 245

AV:31

lcw_1

Leaving Condenser Water

LCDW

R

°F

N/A

-40 to 245

AV:32

lcdw_1

Line Active Current

AMPS_ACT

R

A

N/A

0.0 to 99999.0

AV:8

amps_act_1

Line Active Voltage

VOLT_ACT

R

V

N/A

0.0 to 99999.0

AV:9

volt_act_1

Line Frequency

LINEFREQ

R

Hz

N/A

0 to 99

AV:30

linefreq_1

Line Power Factor

LINE_PF

R

N/A

0.00 to 2.00

AV:34

line_pf_1

Local Schedule

N/A

R

N/A

N/A

No Comm/Normal

BV:2

schedule_1

Occupied?

OCC

R

N/A

NO

NO/YES

BV:10

occ_1

Oil Sump Temperature

OILT

R

°F

N/A

-40 to 245

AV:33

oilt_1

Remote Start Contact

REM_CON

R/W

N/A

OPEN

OPEN/CLOSE

BV:11

rem_con_1

Run Status

STATUS

R

N/A

N/A

0=Timeout,

1=Ready,

2=Recyle,

3=Startup,

4=Running,
5=Demand,

6=Ramping,

7=Autorest,

8=Override,

9=Tripout,

10=Control Test,

11=Lockout,

12=Pumpdown,

13=Prestart

AV:35

status_1

Service Ontime

S_HRS

R/W

hr

N/A

0 to 32767

AV:36

s_hrs_1

Surge Line Delta T

DELTA_TX

R

°F

N/A

0 to 200

AV:38

delta_tx_1

System Alert/Alarm

SYS_ALM

R

N/A

N/A

1=Normal,

2=Alert, 3=Alarm

AV:40

sys_alm_1

611