— OPTIONAL BACNET COMMUNICATIONS WIRING (cont)

To install a BT485 terminator, push the BT485 terminator

on to the BT485 connector located near the BACnet connector.
NOTE: The BT485 terminator has no polarity associated with

it.

To order a BT485 terminator, consult Commercial Products

i-Vu Open Control System Master Prices.
MS/TP WIRING RECOMMENDATIONS — Recommen-

dations are shown in Tables C and D. The wire jacket and UL

temperature rating specifications list two acceptable alterna-

tives. The Halar specification has a higher temperature rating

and a tougher outer jacket than the SmokeGard specification,

and it is appropriate for use in applications where the user is

concerned about abrasion. The Halar jacket is also less likely to

crack in extremely low temperatures.
NOTE: Use the specified type of wire and cable for maximum

signal integrity.

Table C — MS/TP Wiring Recommendations

LEGEND

Fig. E — BT485 Terminator Installation

a48-8582

SPECIFICATION

RECOMMMENDATION

Cable

Single twisted pair, low capacitance, CL2P, 22 AWG (7x30), TC foam FEP, plenum rated cable

Conductor

22 or 24 AWG stranded copper (tin plated)

Insulation

Foamed FEP 0.015 in. (0.381 mm) wall 0.060 in. (1.524 mm) O.D.

Color Code

Black/White

Twist Lay

2 in. (50.8 mm) lay on pair 6 twists/foot (20 twists/meter) nominal

Shielding

Aluminum/Mylar shield with 24 AWG TC drain wire

Jacket

SmokeGard Jacket (SmokeGard PVC) 0.021 in. (0.5334 mm) wall 0.175 in. (4.445 mm) O.D.
Halar Jacket (E-CTFE) 0.010 in. (0.254 mm) wall 0.144 in. (3.6576 mm) O.D.

DC Resistance

15.2 Ohms/1000 feet (50 Ohms/km) nominal

Capacitance

12.5 pF/ft (41 pF/meter) nominal conductor to conductor

Characteristic Impedance

100 Ohms nominal

Weight

12 lb/1000 feet (17.9 kg/km)

UL Temperature Rating

SmokeGard 167°F (75°C)
Halar -40 to 302°F (-40 to 150°C)

Voltage

300 Vac, power limited

Listing

UL: NEC CL2P, or better

AWG

American Wire Gage

CL2P

Class 2 Plenum Cable

DC

Direct Current

FEP

Fluorinated Ethylene Polymer

NEC

National Electrical Code

O.D.

Outside Diameter

TC

Tinned Copper

UL

Underwriters Laboratories