Fire Rated Enclosure
Installation Technique and Design
Advisory Manual
Good Installation Example
• Two layers of insulation tight against duct
• ½” Stainless steel bands on maximum 12” centers
• Bands centered on overlaps
• Duct supports dropped below insulation
• Proper size hanger rod and support, spaced maximum 60” apart
• Access doors installed at change in direction on duct
• FastDoor XL system for access doors
P029_Install_PS_2 2014.indd 27