beautypg.com

FloAire Pyroscat Enclosure User Manual

Page 13

background image

www.morganthermalceramics.com

Page 12

P029_02:2014

Fire Rated Enclosure

Installation Technique and Design

Advisory Manual

Re:

Equivalency of Thermal Ceramics FireMaster

®

FastWrap

®

XL and Pyroscat

®

Duct Wrap XL

This is to advise that both the Pyroscat and FireMaster brands of fire rated duct wrap are manufactured by the
Thermal Ceramics business of Morgan Advanced Materials in our Augusta, GA facility. The FireMaster FastWrap
XL and the Pyroscat Duct Wrap XL should be accepted as equivalents in all applications and installed in the same
manner as described in the Thermal Ceramics installation manual. Both products may be installed on the same
grease or HVAC duct. The two products have the properties shown in the following table:

Property

FireMaster FastWrap XL

Pyroscat DuctWrap XL

Manufacturing Location

Augusta, GA, USA

Augusta, GA, USA

Composition

High Temperature

Low Biopersistence Fibers

High Temperature

Low Biopersistence Fibers

Temperature Limit

Over 2192°F

Over 2192°F

Thickness

1-1/2”

1-1/2”

Density

6 pounds per cubic foot

6 pounds per cubic foot

Width

24” & 48” wide

24” & 48” wide

Length

25 ft. long

25 ft. long

R Value

7.3 per layer

7.3 per layer

Thermal Conductivity at 500°F

0.42 BTU•inch/Hr•Ft

2

•°F

0.42 BTU•inch/Hr•Ft

2

•°F

Thermal Conductivity at 1800°F

1.96 BTU•inch/Hr•Ft

2

•°F

1.96 BTU•inch/Hr•Ft

2

•°F

Area Weight

0.75 lbs per sq. ft.

0.75 lbs per sq. ft.

Fiber Fill Color

White

White

Foil Encapsulation

Fully Encapsulated, Purple Print

Fully Encapsulated, Black Print

Meets 2003 IMC

YES

YES

Flame spread & smoke

developed (UL 723)

Blanket: 0 flame, 0 smoke

Blanket: 0 flame, 0 smoke

developed (UL 723)

Encapsulated: 5 flame, 5 smoke

Encapsulated: 5 flame, 5 smoke

UL Listing

(Grease Duct per ASTM E2336) HNKT G18

HNKT G18

OPL Listing

(Grease Duct Clearance per

UL 1978)

TC/BI 120-01

TC/BI 120-01

UL Listing (HVAC Duct)

HNLJ V19; V1; V2; V29

HNLJ V19; V1; V2; V29

ULC Fire Rated Duct Listings

FRD 3; 4; 5; 6; 7; 18; 28

FRD 3; 4; 5; 6; 7; 18; 28

ICC-ES Report

ESR 2213

ESR 2832

P029_Install_PS_2 2014.indd 12