Fire Rated Enclosure
Installation Technique and Design
Advisory Manual
The integrity of Morgan Thermal Ceramics duct systems is limited to the quality of the installation.
XL003-5
XL Insulation continuous through rated floor/ceiling assembly
XL insulation terminated at the top and bottom
surface of the floor/ceiling assembly
Through Penetration Firestop Systems
Commercial Kitchen Grease Duct Enclosure System
Air Ventilation Duct Enclosure System
XL Insulation continuous through rated wall assembly
XL insulation terminated on both sides of the
rated wall assembly
1
5
2
3
3
5
1
4
2
3
3
5
2
1
4
5
2
5
1
4
4
Firestop Designs per ASTM E814 / UL 1479 - Consult UL / ULC Directories for System Details
C-AJ-7012
C-AJ-7019
C-AJ-7095
C-AJ-7098
F-C-7036
W-J-7086
F-C-7055
C-AJ-7014
C-AJ-7021
W-L-7121
W-L-7145
UL Listing
F- & T-Rating
2-hour
3-hour
1 or 2-hour
2-hour
2-hour
2-hour
1 or 2-hour
1-hour
2-hour
1 or 2-hour
1 or 2-hour
(2) Penetrant
84x24; 26 Ga Duct
84x24; 26 Ga Duct
84x24; 26 Ga Duct
49x24; 16 Ga Duct
39x39; 22 Ga Duct
49x24; 16 Ga Duct
24x12; 16 Ga Duct
4 Dia; 30 Ga Duct
100x100; 26 Ga Duct
30x30; 16 Ga Duct
100x100; 26 Ga Duct
(3) Enclosure Per
V19; FRD3; 5; 18
V2;
V19; FRD3, 5, 18
G18; FRD4; 7
V19; FRD3, 5, 18
G18; FRD4; 7
G18; FRD4; 7
V29; FRD28
V19; FRD3;5; 18
G18; FRD4; 7
V19; FRD3; 5; 18
(1) Floor/Wall
Concrete/CMU
Concrete/CMU
Concrete/CMU
Concrete/CMU
Concrete/CMU
Concrete/CMU
Wood/Gyp Floor
Wood/Gyp Floor
Concrete/CMU Wall
Gyp Wall
Gyp Wall
wrap through
(4) Termination
wrap through
terminate at
terminate at
wrap through
wrap through
wrap through
wrap through
terminate at
wrap through
terminate at
1/2 in; STI; Tremco
(5) Firestop Sealant Details
1/2 in; STI; Tremco
1/4 in; STI; Tremco
1/4 in; STI; Tremco
1/4 in; STI Hilti; Rectorseal; Tremco
1/4 in; STI; Hilti; Rectorseal; Tremco
1/4 in; STI; Hilti; Rectorseal; Tremco
1/4 in; STI
1/4 in; STI
1/4 in; STI; Hilti; Rectorseal; Tremco
5/8 in; STI
Packing
Packing
Packing
Packing
P029_Install_PS_2 2014.indd 14