Technical data – EVCO EPV4TBR Hardware manual User Manual
Page 18
Evco S.p.A.
Vtouch | Hardware manual ver. 1.01 | Code 114VTOUHWE01
page 18 of 22
7.
TECHNICAL DATA
7.1. Technical data
Purpose of control:
user interface for programmable controllers.
Construction of control:
electronic device to be incorporated.
Box:
self-extinguishing transparent.
Size:
118.0 x 111.0 x 26.7 mm (4.645 x 4.370 x 1.051 in).
Size refers to the interface with connector 1 and connector 2 properly plugged.
Installation:
the installation is possible:
- by
panel
-
built-in by wall, in traditional box (like "506" by BTicino)
-
by wall, on the support CPVW00 by Evco (to order separately); look at chapter
6 (ACCESSORIES).
Fixing screws are always supplied by the builder.
At the front of the interface one can apply the plates CPVP* by Evco (to order separately, made in
plastic material and available in two different colorations, white and black); look at chapter
6 (ACCESSORIES).
Frontal protection degree:
IP40 (IP65 for panel mounting with gasket 0027000007, to order separately); look at chapter
6 (ACCESSORIES).
Connections:
extractable male + female terminal blocks (power supply and CAN port), 6 poles telephone connector
(programming port).
The maximum length of the connecting cables of the CAN port of the interface depends on the baud
rate of the CAN communication, as follows:
-
1,000 m (3,280 ft) with baud rate 20,000 baud
-
500 m (1,640 ft) with baud rate 50,000 baud
-
250 m (820 ft) with baud rate 125,000 baud
-
50 m (164 ft) with baud rate 500,000 baud.
According to the default settings, the interface recognizes the baud rate automatically, on condition
that it is one of the those mentioned above.
Working temperature:
from 0 to 50 °C (32 to 120 °F, 10 ... 90% of relative humidity without condensate).
Pollution situation:
2 or more.