53u_24_25.pdf, Troubleshooting – Braeburn 5300 2H-2C User Manual User Manual
Page 13

24
25
4
TROUBLESHOOTING
SYMPTOM
POTENTIAL SOLUTION
4
TROUBLESHOOTING
SYMPTOM
POTENTIAL SOLUTION
cont.
cont.
Thermostat turns on
second (auxiliary)
stage of heating or
cooling too quickly or
not quickly enough.
Low battery indicator
is shown in
thermostat display.
Replace back-up batteries as soon as possible. See Low Battery Detection and
Replacement section of this manual.
The room is too
warm or too cold.
See Review Set Temperature section of this manual to verify the current setpoint and
make any modifications that are necessary.
Thermostat display
is blank.
It is possible that AC power is not present at the thermostat and the batteries are fully
discharged. Check fuse, circuit breaker and thermostat wiring as appropriate to verify AC
power is available. Replace batteries before reprogramming thermostat. See Low Battery
Detection and Replacement and Setting Your Energy Saving Program sections of
this manual.
If AC Power is present, call a professional service technician to verify thermostat and
system performance.
Thermostat will not
allow me to program
a setpoint
temperature higher
than 90˚ F (32˚ C).
This is above the normal thermostat temperature setting range of 45˚ to 90˚ F (7˚ to 32˚ C).
HI is shown in the
thermostat display
where the room
temperature is
normally displayed.
The temperature sensed by the thermostat is higher than the 99˚ F (37˚ C) upper limit of
the thermostats display range. The display will return to normal after the sensed
temperature lowers within the 40˚ to 99˚ F (5˚ to 37˚ C) display range. Turn on the cooling
system or use other methods to lower the temperature accordingly.
This condition could occur from the system being turned off during an exceptionally warm
period, or upon installation when the thermostat has been stored for a long period of time
in a warm vehicle or location prior to being installed. The thermostat is equipped with a
mechanical high temperature safety switch that will turn off the system should the
temperature exceed 99˚ F (37˚ C)
.
Thermostat will not
allow me to program
a setpoint
temperature lower
than 45˚ F (7˚ C).
This is below the normal thermostat temperature setting range of 45˚ to 90˚ F (7˚ to 32˚ C).
Fan runs constantly
or for long periods
of time.
Fan control is set to
ON.
Fan control is set to
PROG and is programmed to be on.
Keypad does
not function.
Keypad is locked (check for LOCK segment in display).
Increase or decrease second (auxiliary) stage temperature differential setting as
appropriate to provide the desired performance level. See Setting the First and Second
Stage Differentials section of this manual.