Chapter 4 Wiring
4-3
4
ENGLISH
4-3 Method for Wiring to Signal Input Terminals
As shown in the table below, the SL-R11 is provided with a signal input terminal block. First loosen the
terminal block screws, and then retighten the terminal block screws after inserting the signal cables.
Input terminals
Terminal No.
Name
1, 2
Start / Restart input
3, 4*
1
TEST input
5, 6*
1
M/S SELECT input *
2
7, 8
MPCE MONITOR input
9, 10*
1
E-STOP1 input
11, 12*
1
E-STOP2 input
*1 When the SL-R11 is shipped, short bars are
connected across terminal Nos. 3 and 4, 5 and 6,
9 and 10, and 11 and 12.
To use the functions assigned to these terminals,
remove the short bar and wire the terminal.
*2 Main/Sub select input
See Instruction Man
ual.
MPCE2
MPCE1
T R
POWER
FSD-ON
FSD-OFF
INTERLOCK
LOCKOUT
RESTART
TEST
MPCE
E-STOP1
E-STOP2
CAUTION
Electric shock
2
1
3
Tighten with flat-head
screwdriver
Insert wire
Loosen with flat-head
screwdriver
• Tightening torque
4.4 lb•in (0.5 N•m)
• Wire rating
AWG #22 to 14 (Stranded only, Copper only, min. 60 °C)
• Cable stripping dimension
10mm
(0.39")