beautypg.com

Installation, Controller, Sensor head – KEYENCE EX-500(W) Series User Manual

Page 6

background image

6

INSTALLATION

Controller

The controller can be mounted to a DIN rail. When mounting or
dismounting the controller, pull the claws located at the bottom of
the controller in the direction shown by the arrows. Also, the
controller can be mounted with screws by pulling out the fittings.

Sensor head

Connecting to/disconnecting from the controller

• Plug the sensor head cable into

the connector of the controller until
it clicks. (When connecting an
extension cable to the controller or
the sensor head, follow the same
procedure.)

• When disconnecting the plug, hold

it by the sleeve and pull it out as
shown on the right.

When connecting and disconnect-

ing the plug, be sure to hold it by

the sleeve. If you forcefully pull on

the cable, the cable may break off

from the plug.

Mounting

Nut tightening position
Tighten the nut away from the tip of
the metal case as shown on the right.

Torque values
Tighten the nut according to the
torque values given in the table
below.

EX-008

EX-016

EX-022

10 Nm

20 Nm

30 Nm

(approx. 100 kgf-cm) max. (approx. 200 kgf-cm) max. (approx. 300 kgf-cm) max.

Flush-mounting

The diagram and table below shows the dimensions to use when
flush-mounting a sensor head onto a metal plate.

A (mm)

B (mm)

EX-008

20

11

EX-016

45

20

EX-022

60

25

When mounted with screws

When mounted on DIN rail

Incorrect

Correct

3mm min

øA

B