LEGEND AND NOTES FOR FIG. 41-47

LEGEND

ALARM — Unit Alarm Relay (Critical Fault)
ALM-CM — Alarm/Warning Relay Common
AO

Analog Output

AQUA

Aquastat

BM

Blower Motor

BPS_S — Fan Start/Stop Relay (VFD Bypass Mode)
BR

Blower Relay

BYPAS — VFD Bypass Control
CBR

Circuit Breaker

CC

Compressor Contactor

CCN

Carrier Comfort Network

®

CDWF

Condenser Waterflow Relay

CDWFS — Condenser Waterflow Switch
CLO

Compressor Lockout Control

CMP

Compressor Control Relay

COMPR — Compressor
CSMUX — Signal Multiplexer-Comp Status
DHS

Duct High Static Limit Switch

DO

Digital Output

DSP

Duct Static Pressure Transducer

ECONO — Economizer Valve/Damper Control
EWT

Entering Water Temperature Sensor

FLTS

Filter Status Switch

FREEZ — Freeze Thermostat (Water Economizer)
FSD

Fire Alarm/Shutdown

GND

Ground

HIR

Heat Interlock Relay

HPS

High Refrigerant Pressure Switch

LPS

Low Refrigerant Pressure Switch

MA_RA

Mixed/Return Air Temperature Sensor

MBVR

Motorized Ball Valve Relay

MSR

Local/Remote Control Relays

OLR

Compressor Motor Protector

PCB1

Unit Control Board

PCB2,3

I/O Expansion Board

PHASE

Phase/Rotation Monitor

PHASER

Phase Monitor Relay

RAT

Return Air Thermostat

RESET

External Reset

ROCC

Remote Occupancy

SAT

Supply Air Temp. Sensor

SPT

Space/Zone Temperature Sensor

SF

Supply Fan Start/Stop Relay

SPEED

0-10 VDC Signal Isolator for VFD

SW

Switch

T

Transformer

TB2

Terminal Block for Field Connections

TRANS

Transformer

TRMCT

VAV Terminals Control

TRMOP

VAV Terminals Open

VENTR

Ventilation Output

VFD

Variable Frequency Drive

WARN

Unit Warning Relay (Non-Critical Fault)

Factory Wiring

Field Wiring

NOTES:

1. Partial wiring shown on both power and control diagrams.
2. Class 2 transformer TRANS-1 is wired into separate circuit. Do not interconnect other

transformers or circuits; circuit separation or compressor transformers from low voltage
control panel transformers shall be maintained.

3. Shielded wire shall have drain wire connected to VFD ground screw. The floating end

of the drain wire shall be insulated.

4. Shielded wire shall have drain wire connected to the control panel, adjacent to the

PCB. The floating end of the drain wire shall be insulated.