7. Enter the day of the month. Press

then press

. The LID display will show:

Year
95

8. Enter the last two digits of the current year. Press

then press

. The LID display will show:

Update Clock
No

9. Press 1 and then

to update the clock. The LID

display will flash. Press

twice to view the de-

fault display and the clock should update to the input time
and date.

CONFIGURE SCHEDULES — Schedules are one method

of starting and stopping the unit at specified intervals. To con-

figure the schedules, perform the following procedure:

1. Press 1 and then

. The LID display will show:

Occupancy Algorithm

2. Press

. The LID display will show:

Time Schedule
Enter to Select

3. Press

. If the LID display shows “MODE 0,”

then the user is in Maintenance mode and the LID display
is showing the maintenance information for the occupan-
cy schedule. Press

to enter the configura-

tion mode. The LID display will show:
Manual Override Hours
0 hours
This is the first configuration for each occupancy

algorithm and is used to put the schedule in or out of

occupancy override for the number of hours entered.

4. Press

. The LID display will show:

Period 1: Day of week
00000000
The eight digits represent the certain days of the week or

holidays this period should apply to: M, Tu, W, Th, F, Sa,

Su, and Hol, respectively. Enter a series of 0s or 1s with a

1 corresponding to the days that this period should apply

to and a 0 for the days that this schedule should not apply

to. As an example, entering 11111000 would make the

schedule apply to days Monday through Friday and not

apply to Saturday, Sunday, or Holidays.

5. Press the

button. The LID display will show:

Period 1 occupied from
00:00

6. Input the occupancy start time for this period.

NOTE: 12.00 represents 12:00 pm.

7. Press the

to input the occupied to time for period 1.

8. Input the days and times for periods 2 through 8 as

required.

9. Press

to leave the occupancy programming.

PROGRAM SET POINTS — To program the set points, per-

form the following procedure:

1. Press 2 and then

. The LID display will show:

Setpoint Schedule

2. Press

. The LID display will show:

Supply Fan Status
SETPT01

3. Press .
4. If “No Maintenance” is displayed, press

to

view the set point information. The LID display will
show:
Occupied Lo Setpoint
0.30 in. H2O
This is the pressure set point below which the fan is con-

sidered to be off.

5. Press

. The LID display will show:

Occupied Hi Setpoint
0.40 in. H2O
This is the pressure set point above which the fan is con-

sidered to be on.
The down or up arrow will also display the unoccupied

low and high temperature set points. These values should

be kept the same as the occupied values.

6. To view set points 02-09, use the following sequence:

Press 2 and then

. The LID display will show:

Setpoint Schedule
Press

. The LID display will show:

Supply Fan Status
SETPT01
Press

to scroll down to the desired set point. Press

to select.

To view another point, press

once to move up

one menu level. Then press

to scroll down to

the desired set point and press

to select.

7. Pressing the

button will take the user out of the

set point configuration mode.
Set point functions are as follows:
Setpoint 02 (VAVRESETbaseline) internally coordinates

the supply air set point reset in several of the algorithms

and cannot be modified.
Setpoint 03 (Heat/Cool Mode & Reset) is used for com-

parison by the unit to return air, space temperature, or

average space temperature through linkage to determine

when to start reset of the supply air when occupied, when

to turn on heat and disable cooling when occupied,

and when to bring the unit on for unoccupied heating or

cooling.
Setpoint 05 (Supply Static Pressure) is used to set the sup-

ply air static pressure the unit should maintain. Only the

Occupied Low set point may be modified. The other

values will change to the Occupied Low value shortly

after it is modified so that all the values remain the same.

The set point in the static pressure control algorithm will

also follow and cannot be modified in the algorithm con-

figuration screens.
Setpoint 06 (Supply Air Temperature) is the supply air

temperature set point. Only the Occupied Low set

point may be modified. The other values will change

to the Occupied Low value shortly after it is modified

so that all the values remain the same. The set point in

DX VAV staging and some of the other algorithms will

also follow and cannot be modified in the algorithm

configuration screens.
Table 21 lists the available controller set points and

their default values. Refer to 50BV,XJ Controls, Opera-

tion and Troubleshooting manual for additional set point

descriptions.