Carrier OMNIZONE 50BV020-064 User Manual
Page 32
32
Table 14 — Fan Performance — 50BVC,E,Q024
LEGEND
NOTES:
1. Units are available with the following motor and drive combina-
tions: 2, 3, and 5 HP standard drive; 2, 3 HP medium static
drive.
For 2, 3 HP standard drives, the drive range is 753 to 952 rpm.
For medium static drives, the drive range is 872 to 1071 rpm.
For 5 HP standard drives, the drive range is 967 to 1290 rpm.
2. Italics indicates field-supplied drive required.
3.
Do not operate in shaded area.
4. Static pressure losses must be applied to external static pres-
sure before entering the fan performance table.
5. Interpolation is permitted, extrapolation is not.
6. Fan performance is based on filter, unit casing and wet coil
losses.
7. Bhp values are per fan. Watts values are per motor. Unit has
2 supply fans and 2 motors.
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
5,000
—
—
—
—
—
—
638
545
0.61
—
—
—
—
—
—
5,500
—
—
—
—
—
—
655
641
0.72
725
755
0.85
—
—
—
6,000
—
—
—
608
641
0.72
676
755
0.85
742
878
0.99
807
1001
1.13
6,500
—
—
—
636
755
0.85
699
878
0.99
761
1010
1.14
821
1142
1.29
7,000
604
774
0.87
666
906
1.02
726
1029
1.16
784
1170
1.32
841
1311
1.48
7,500
634
916
1.03
693
1057
1.19
750
1189
1.34
805
1330
1.50
858
1480
1.67
8,000
667
1085
1.22
723
1226
1.38
777
1377
1.55
829
1526
1.72
880
1676
1.89
8,500
700
1273
1.43
753
1423
1.60
804
1573
1.77
853
1732
1.95
902
1836
2.13
9,000
735
1480
1.67
785
1638
1.84
833
1745
2.02
881
1908
2.21
927
2071
2.40
9,500
769
1713
1.93
816
1827
2.12
863
1989
2.31
908
2152
2.50
952
2323
2.69
10,000
802
1908
2.21
848
2080
2.41
892
2251
2.61
936
2422
2.81
978
2624
3.01
AIRFLOW
(cfm)
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
Rpm
Watts
Bhp
5,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
5,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
6,000
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
6,500
881
1283
1.44
—
—
—
—
—
—
—
—
—
—
—
—
7,000
897
1451
1.63
951
1601
1.80
—
—
—
—
—
—
—
—
—
7,500
911
1629
1.83
963
1727
2.00
1014
1881
2.18
—
—
—
—
—
—
8,000
930
1781
2.07
979
1935
2.24
1028
2098
2.43
1076
2260
2.62
1124
2422
2.81
8,500
950
1989
2.31
997
2152
2.50
1043
2323
2.69
1089
2485
2.88
1134
2697
3.09
9,000
973
2233
2.59
1018
2404
2.79
1062
2576
2.99
1106
2779
3.18
1149
2960
3.39
9,500
996
2494
2.89
1039
2697
3.09
1081
2879
3.30
1123
3060
3.51
1165
3251
3.73
10,000
1020
2806
3.22
1061
2988
3.42
1102
3178
3.64
1142
3360
3.85
1182
3559
4.08
Bhp
— Brake Horsepower Input to Supply Fan
Watts — Input Power to Supply Fan Motor