14 manual mode – STIEBEL ELTRON SOM 10 User Manual
Page 71

en
71
14 Manual mode
In the Manual mode menu, the operating mode of
all relays in the controller and in connected modules
can be adjusted.
All relays are displayed in numerical order, first those
of the controller, then those of the individual modules
connected. Modules are listed in numerical order.
Under the menu item All relays..., all relays can be
switched off (Off) or set to automatic mode (Auto)
at once.
Off
= Relay is switched off (manual mode)
Auto = Relay is in automatic mode
The operating mode can be selected for each indi-
vidual relay, too. The following options are available:
Off
= Relay is switched off (manual mode)
Min. = Relay active with minimum speed
(manual mode)
Max. = Relay active at 100 % speed (manual mode)
Auto = Relay is in automatic mode
Note:
Always adjust the operating mode back to
Auto when the control and service work is
completed. Otherwise normal operation will
not be possible.
Adjustment channel
Description
Adjustment range / selection
Factory setting
Relays R1 ... X
Operating mode selection
Max, Auto, Min, Off
Auto
All relays...
Operating mode selection for all
relays
Auto, Off
Off
Manual mode