Heat exchange
The heat exchange function can be used for transfer-
ring heat from a heat source to a heat sink.
The allocated relay is energized when all switch-on
conditions are fulfilled:
• the temperature difference between the allocated
sensors has exceeded the switch-on temperature
difference
• the temperature at the heat source sensor has
exceeded the minimum temperature
• the temperature at the heat sink sensor has fallen
below the maximum temperature
If ∆Tset is exceeded, pump speed control will come
into effect. For every deviation of 2 K [4 °Ra], the
pump speed will be adjusted by 10 %.
Sensor Source
Relay
Sensor Sink
Adjustment channel Description
Adjustment range / selection Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. So.
Heat source sensor selection
system dependent
system dependent
Sen. Sink
Heat sink sensor selection
system dependent
system dependent
∆Ton
Switch-on temperature difference
1.0 ... 30.0 K [2.0 ... 60.0 °Ra] 6.0 K [12.0°Ra]
∆Toff
Switch-off temperature difference
0.5 ... 29.5 K [1.0 ... 59.0 °Ra] 4.0 K [8.0°Ra]
∆Tset
Set temperature difference
1.5 ... 40.0 K [3.0 ... 80.0 °Ra] 10.0 K [20.0°Ra]
Min. speed
Minimum speed
30 ... 100 %
30 %
Tmax
Maximum temperature of the store
to be loaded
10 ... 95 °C [50 ... 204 °F]
60 °C [140 °F]
Tmin
Minimum temperature of the store
to be loaded
10 ... 95 °C [50 ... 204 °F]
10 °C [50 °F]
Funct.
Activation / Deactivation
Activ., Deactivated
Deactivated
Arrangement / Opt. functions / Add new function... / Heat exchange