Twin pump
The Twin pump function controls the equal distri-
bution of pump runtime in systems with two equally
usable pumps.
If the allocated relay has exceeded its adjusted run-
time and the next switch-on process is imminent, the
reference relay is switched on instead. All characteris-
tics are adopted.
If the reference relay has in turn exceeded its runtime
as well, the first relay is switched on again in the next
switch-on process.
Additionally, the Flow rate monitoring option can
be activated in order to activate the twin pump in the
case of a flow rate error. When the flow rate moni-
toring option is activated, two additional adjustment
channels appear for allocating a sensor and adjusting
a delay time.
If the flow rate monitoring option is activated, an er-
ror message will appear when no flow rate is detec-
ted at the allocated sensor after the Delay time has
passed. The active relay is considered as defective and
will be blocked until the error message has been ack-
nowledged. The second relay will be activated instead.
The twin pump function will pause until the error
message has been acknowledged.
When the error message is acknowledged, the con-
troller runs a test during which it will energize the
relay and again monitor the flow rate.
Adjustment channel Description
Adjustment range / selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Ref. relay
Reference relay selection
system dependent
system dependent
Runtime
Pump runtime
1 ... 48 h
6 h
Flow rate mon.
Flow rate monitoring option
Yes, No
No
Flow rate sen.
Flow rate sensor selection
Imp1 ... Imp3, Ga1, Ga2, Gd1, Gd2 Imp1
Delay
Delay time
1 ... 10 min
5 min
Funct.
Activation / Deactivation
Activ., Deactivated
Deactivated
Solar / Opt. functions / Add new function... / Twin pump
relay
reference relay
Exemplary figure of twin pumps in the solar flow
with upstream flowmeter