Return preheating
The return preheating function can be used for trans-
ferring heat from a heat source to the heating circuit
return.
The allocated relay is energized when both switch-on
conditions are fulfilled:
• the temperature difference between the allocated
sensors has exceeded the switch-on temperature
difference
• the temperature at the outdoor temperature
sensor has fallen below the adjusted outdoor
temperature
With the summer switch-off option, the return pre-
heating can be suppressed outside the heating period.
If the heating circuit concerned is controlled by the
controller, the adjustments automatically adapt to the
heating circuit.
Sensor HS
Relay
Sensor
Return
Adjustment channel Description
Adjustment range / selection Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. Return
Return sensor selection
system dependent
system dependent
Sen. HS
Heat source sensor selection
system dependent
system dependent
∆Ton
Switch-on temperature difference 2.0 ... 30.0 K [4.0 ... 60.0 °Ra] 6.0 K [12.0 °Ra]
∆Toff
Switch-off temperature difference 1.0 ... 29.0 K [2.0 ... 58.0 °Ra] 4.0 K [8.0 °Ra]
Summer off
Summer switch-off option
Yes, No
No
Sensor
Outdoor sensor selection
system dependent
system dependent*
Toff
Switch-off temperature
10 ... 60 °C [50 ... 140 °F]
20 °C [68 °F]
Funct.
Activation / Deactivation
Activ., Deactivated
Deactivated
Arrangement / Opt. functions / Add new function... / Ret. preheat.
* When a heating circuit has been activated, this
adjustment is determined by the corresponding
parameter in the heating circuit menu.