STIEBEL ELTRON SOM 10 User Manual
Page 58

en
58
Arrangement / Opt. functions / Add new function... / Function block
Adjustment channel Description
Adjustment range / selection Factory setting
Relay
Relay
R2
R2 ... R14
Thermostat a
Thermostat a
Yes, No
No
Th-a on
Switch-on temperature Thermostat a -40 ... 250 °C [-40 ... 482 °F]
40 °C [104 °F]
Th-a off
Switch-off temperature Thermostat a -40 ... 250 °C [-40 ... 482 °F]
45 °C [114 °F]
Sensor
Sensor thermostat a
S1 ... S12
S4
Thermostat b
Thermostat b
Yes, No
No
Th-b on
Switch-on temperature Thermostat b -40 ... 250 °C [-40 ... 482 °F]
40 °C [104 °F]
Th-b off
Switch-off temperature Thermostat b -40 ... 250 °C [-40 ... 482 °F]
45 °C [114 °F]
Sensor
Sensor thermostat b
S1 ... S12
S5
∆T function
Differential function
Yes, No
No
∆Ton
Switch-on temperature difference
1.0 ... 50.0 K [2.0 ... 100.0 °Ra] 5.0 K [10.0 °Ra]
∆Toff
Switch-off temperature difference
0.5 ... 49.5 K [1.0 ... 99.0 °Ra] 3.0 K [6.0 °Ra]
Sen. So.
Heat source sensor
Controller S1 ... S12
S6
Sen. Sink
Heat sink sensor
Controller S1 ... S12
S7
Timer
Timer
-
-
Days of the week
Day selection
All days, Monday ... Sunday,
Continue
-
Timer
Time frame adjustment
00:00 ... 23:45
-
Funct.
Activation/Deactivation
Activ./Deactivated
Deactivated