STIEBEL ELTRON SOM 10 User Manual
Page 53

en
53
Solid fuel boiler
The solid fuel boiler function can be used for transfer-
ring heat from a solid fuel boiler to a store.
The allocated relay is energized when all switch-on
conditions are fulfilled:
• the temperature difference between the allocated
sensors has exceeded the switch-on temperature
difference
• the temperature at the solid fuel boiler sensor has
exceeded the minimum temperature
• the temperature at the store sensor has fallen
below the maximum temperature
If ∆Tset is exceeded, pump speed control will come
into effect. For every deviation of 2 K [4 °Ra], the
pump speed will be adjusted by 10 %.
Adjustment channel Description
Adjustment range / selection Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. Boiler
Solid fuel boiler sensor selection
system dependent
system dependent
Sen. Store
Store sensor selection
system dependent
system dependent
∆Ton
Switch-on temperature difference 1.0 ... 30.0 K [2.0 ... 60.0 °Ra] 6.0 K [12.0°Ra]
∆Toff
Switch-off temperature difference 0.5 ... 29.5 K [1.0 ... 59.0 °Ra] 4.0 K [8.0°Ra]
∆Tset
Set temperature difference
1.5 ... 40.0 K [3.0 ... 80.0 °Ra] 10.0 K [20.0°Ra]
Min. speed
Minimum speed
30 ... 100 %
30 %
Tmax St.
Maximum temperature
10 ... 95 °C [50 ... 204 °F]
60 °C [140 °F]
Tmin boiler
Minimum temperature
10 ... 95 °C [50 ... 204 °F]
60 °C [140 °F]
Funct.
Activation / Deactivation
Activ., Deactivated
Deactivated
Arrangement / Opt. functions / Add new function... / Solid fuel boiler
Sensor Store
Relay
Sensor Solid fuel boiler