STIEBEL ELTRON SOM 10 User Manual
Page 33

en
33
In systems with 2 or more stores, the correspon-
ding number of seperate menu items (Store 1 to
Store 5) is displayed instead of Store.
For each store, an individual ∆T control, a set and a
maximum temperature, the priority, a hysteresis, a rise
value, a minimum runtime and a minimum pump speed
can be adjusted.
In multi-store-systems with differing Store set / Ma-
ximum store temperatures, all stores are loaded up
to their Stset temperatures first (according to their
priority and the store sequence control). Only when
all stores have exceeded Stset will they be loaded
up to their Stmax temperatures, again according to
their priority and the store sequence control.
Store (1 / 2 / 3 / 4 / 5)
Solar / Basic settings / Store (1 / 2 / 3 / 4 / 5)
Adjustment channel Description
Adjustment range / selection Factory setting
∆Ton
Switch-on temperature difference 1.0 ... 20.0 K [2.0 ... 40.0°Ra] 6.0 K [12.0 °Ra]
∆Toff
Switch-off temperature difference 0.5 ... 19.5 K [1.0 ... 39.0°Ra] 4.0 K [8.0 °Ra]
∆Tset
Set temperature
1.5 ... 30.0 K [1.5 ... 60.0°Ra] 10.0 K [20.0 °Ra]
Stset
Store set temperature
4 ... 95 °C [40 ... 204 °F]
45 °C [114 °F]
Stmax
Maximum store temperature
4 ... 95 °C [40 ... 204 °F]
60 °C [140 °F]
Priority
Priority
1
1 ... 5
(system-dependent)
HysSt
Hysteresis maximum store
temperature
0.1 ... 10.0 K [0.2 ... 20.0°Ra] 2.0 K [4.0 °Ra]
Rise
Rise
1.0 ... 20.0 K [2.0 ... 40.0°Ra] 2.0 K [4.0 °Ra]
tmin
Minimum runtime
0 ... 300
180
Min speed.
Minimum speed
30 ... 100 %
30 %
Deactivated
Blocked for solar loading
Yes, No
No