11 hqm – STIEBEL ELTRON SOM 10 User Manual
Page 67

en
67
adjustment channel Description
Adjustment range / selection
Factory setting
Demand
Demand relay selection
system dependent
system dependent
Loading pump
Loading pump option
Yes, No
No
Relay
Loading pump relay selection
system dependent
system dependent
Overrun time
Overrun option
Yes, No
No
Duration
Overrun time
1 ... 10 min
1 min
Mode
Operating mode
Boiler, Therm.
Therm.
Sensor 1
Sensor 1
system dependent
system dependent
Sensor 2
Sensor 2 (only if Mode = Boiler) system dependent
system dependent
Ton
Switch-on temperature
0 ... 94 °C [32 ... 202 °F]
40 °C [104 °F]
Toff
Switch-off temperature
1 ... 95 °C [34 ... 204 °F]
45 °C [114 °F]
Timer
Timer option
Yes, No
No
Timer
Timer
-
-
Days of the week
Day selection
All days, Monday ... Sunday,
Continue
-
Timer
Time frame adjustment
00:00 ... 23:45
-
Funct.
Activation / Deactivation
Activ., Deactivated
Deactivated
Heating / Opt. functions / Add new function... / DHW heating
11 HQM
In the HQM menu, up to seven internal heat quantity
measurements can be activated and adjusted.
By selecting the menu item New HQM, a new heat
quantity measurement can be activated.
A menu opens in which all adjustments required for
the heat quantity measurement can be made.
If the Flow rate sensor option is activated, the im-
pulse input or, if available, a Grundfos Direct Sensor™
can be selected. Grundfos Direct Sensors™ are only
available if they have been previously registered in the
In-/Outputs menu. The impulse rate must be adjusted
in that menu as well.
If the Flow rate sensor option is deactivated, the
controller calculates the heat quantity by means of a
fixed flow rate value. This is called heat quantity balan-
cing. For this purpose, the flow rate must be read from
the flowmeter at 100 % pump speed and adjusted in
the adjustment channel Flow rate. In addition to that,
a Relay must be allocated. Heat quantity balancing is
in effect whenever the allocated relay is active.
In the adjustment channel Fluid type, the heat trans-
fer fluid must be selected. If either Propylene glycol